Min. Order: | 1 Set/Sets |
---|---|
Trade Term: | FOB |
Payment Terms: | T/T |
Supply Ability: | 1000 sets per month |
Place of Origin: | Hubei |
Location: | Wuhan, Hubei, China (Mainland) |
---|---|
Business Type: | Manufacturer, Trading Company, Distributor/Wholesaler |
Main Products: | Insulating Oil Tester, SLQ Primary Current Injection Test Set, HYVA-404 CT PT Analyzer, HYLB-601 Instantaneous Signal Recorder, HYGK-306 Circuit Breaker Analyzer |
Model No.: | HYHL-III |
---|---|
Means of Transport: | Air |
Brand Name: | Huaying |
Production Capacity: | 1000 sets per month |
Packing: | wooden case |
Delivery Date: | 7 working days |
Product model: HYHL-100A/HYHL-III | |||||||
Product brief introduction: | |||||||
Contact resistance tester output DC 100A current to test the contact resistance | |||||||
It is designed according to IEC62271. | |||||||
The main application of the tester is measurement of circuit breaker contact resistance. | |||||||
All the test results of the tester could be print by the micro-printer which is integrated in the tester. | |||||||
Also all the test results saved in the tester could be upload to PC computer and then convert to MS WORD document. |
Product technique index:
1. Measurement range: 0-1999.9 μΩ
2. Resolution:0.1 μΩ
3. Test current: DC 200A/100A for different selection
4. Maximum error< 0.5 %RDG+0.05%FS
5. Display mode: LCD
6. Save no more than 100 groups of data
7. RS232 computer interface
8. Rated power supply:AC220V
9. Size: 340 × 280 × 210mm3
10. Environment temperature:-10 ℃~+40 ℃ Relative humidity<80%
Product picture:100A 200A same panel design