switch tester switch analyzer circuit breaker analyzer

1.0~2.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: L/C, D/P, D/A, T/T, WU
Supply Ability: 100 sets
Place of Origin: Hubei

Company Profile

Location: Wuhan, Hubei, China (Mainland)
Business Type: Manufacturer, Trading Company, Distributor/Wholesaler
Main Products: Insulating Oil Tester, SLQ Primary Current Injection Test Set, HYVA-404 CT PT Analyzer, HYLB-601 Instantaneous Signal Recorder, HYGK-306 Circuit Breaker Analyzer

Product Detail

Model No.: 307
Means of Transport: Ocean, Air
Brand Name: Huaying
Production Capacity: 100 sets
Packing: wooden case
Delivery Date: 7 working days
Show

Product Description

 Circuit breaker analyzer introduction:

 1) Measurement of closing time, opening time, time spread between poles, time spread between units of one pole, bounces etc.
 2) Measurement of closing speed, opening speed and average speed.
 3) Measurement of clearance between open contacts, over travel, overshoot travel and total travel.
 4) Measurement of closing coil current time curve, opening coil current time curve and the maximum coil current
 5) Test travel time curve, speed time curve and acceleration time curve
 6) Measurement of pre-insertion resistance value and pre-insertion ion time.
 7) Test contact resistance 
 8) Measurement of dynamic resistance time curve and length for arcing contacts
 9) Vibration test, including vibration fingerprint curve acquisition, management, and vibration fingerprint curve automatic matching.
 10) CO-t1-CO,O-t-CO-t1-CO,CO rated operating sequence verification test.
 11) Drawing Envelopes for reference travel curve and compare travel curve with envelopes
 12) Mechanical travel curve automatic compare with saved travel curve
 13) Measurement of CO time (close-open time) and OC time (Opening-Closing time)
 14) Graphite contact closing time, opening time, dynamic resistance curve measurement
 15) Zoom, editors, statistics and analysis for measurement curves.
 16)12.1-inch touch screen for control and data input
 17) Built-in micro printer for test result printout.
 18) Generate WORD format test report automatically (all reports and data can be exported through Flash disk).

 Circuit breaker analyzer technical index:

  1) 12 channels for time measurement (3-channel supports both the time contact and resistance contact time, 6-channel isolated  contacts for cascaded unit measurement of pole)
  2) Time measurement 
      Range: 4000ms
      Error :< 0.1ms
      Resolution: 0.01ms
   3) Travel measurement according to sensor:
   Linear resistance sensor:
   Measurement range: 0~250mm; resolution: 0.01mm; error: <0.5mm
   Measurement range: 0~25mm; resolution: 0.01mm; error: <0.05mm
   Angle resistance sensor:
   Measurement range: 0~360°; resolution: 0.01°; error: <0.5°
  4) Pre-insertion resistance measurement
    Range: 50~5000ohm; error :<1%RDG+2D
  5) Dynamic resistance measurement
     Test current: 25~100A
     Measurement error :< 1%RDG+2D 
   6) Contact resistance measurement 
     Range:0--10mohm 
     Error <0.5%RDG+0.05%FS
     Range: 0-2mohm;
     Error: <0.5%RDG+2D
  7) Speed measurement
    250mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D
    25mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D
    Angle sensor: 0~20m/s; error: <0.5%RDG+2D
    Acceleration sensor: 0~20m/s; error: <5%RDG+2D
  8) Coil current measurement
    Range: 0~20A; resolution: 0.001A; error: <0.01A
  9) Vibration measurement 
    Range: 0~5000G; error: <3%
  10) Internal DC power source: voltage: 12~265V; current:0~20A
  11) Built-in 8G storage memory and 2 USB interface for data export and external keyboard or mouse connection
  12) Power supply: AC220V±10%; 50Hz±10%
  13)Working environment: temperature: -10~50°C;  Humidity: <80%

contact at whhy818@163.com, chloe shuyue wang, skype wangshuyue1991.