Model No.: | KXR28-25/36/93 |
---|---|
Means of Transport: | Ocean, Air, Land |
Type: | Others |
Poles Number: | 3 |
Brand Name: | CHKX |
Rated working current Ie(AC-3 (380V)): | 9-95 |
Rated working current Ie(AC-3 (6600V)): | 6.6-49 |
Rated working voltage(Ue)V: | 690,380 |
Rated isolating voltage(Ui)V: | 690 |
Auxiliary contact conventional free air heating current Ith (A): | 10 |
Action mechanic: | directing acting type |
Installation altitude: | can't exceed 2000m |
Pullution degree: | III |
Installation degree: | III |
Power supply frequency: | 50,60 |
Production Capacity: | 100000PCS/PER MONTH |
Packing: | Neutral or customized |
Delivery Date: | 30 days or customized |
KXR28 thermal overload relay series
◎Summarization
◆KXR28 series thermal overload relay (hereinafter referred tor as thermal relay) apply to AC 50Hz/60Hz, rated voltage till 660V, current 0.1-93A AC electric motor permanent working or discontinuous permanent working for overload or open-phase protection.
◆Thermal relay have open-phase protection, temperature compensation, operation indication, auto and manual reset and stop function, reliable action. Can plug-in install with contactor, also can install it independently and combined with relative AC contactor to consist of electromagnet starter.
◆According to GB14048.4, GB14048.5, IEC60947-4-1 etc standard,
◎Model and meaning:
◎Structure feature:
◆Three phase sheet metal type, trip type 10A
◆Have open-phase and overload protection
◆Have setting current continuous adjustable device
◆Temperature compensation
◆Operating indication
◆Test mechanism
◆With stop button
◆With auto and manual reset button
◆On the device have separable one normally open and one normally close contact
◆Installation method: plug-in install with contactor or install independently
◎Normal working criteria
◆Altitude: not exceed 2000m
◆Surrounding air temperature: -5℃~40℃, and 24h's average temperature should lower than +35℃
◆atmospheric conditions: Atmospheric relative humidity should lower than 50% when the temperature is +40℃, higher relative humidity is acceptable when the temperature lower than +40℃, max relative humidity can reach 90% when the temperature at +20℃, should have special policy in condensation condition which may caused by temperature changing.
◆Pollution degree: III
◆Installation surface vertical gradient can't exceed 5°
◆The place should without explosion dangerous media/neurogen, and the media should without corrosive goods to metal and damage goods to isolator and no conducting dust
◆The place should have anti snow and rain device and shouldn't full of vapour
◆ The place shouldn't have obvious shake, shock and impact
◎Main technical parameter
◆Protection characteristic
Item | No. | Rated current multiple | Action time | Testing criteria | |
1 | 1.05 | Non action in 2h | Cold start | ||
Overload protection | 2 | 1.2 | Action in 2h | Hot(after No. 1) start | |
3 | 1.5 | Action in 2m | Hot(after No. 1) start | ||
4 | 7.2 | 2s﹤Tp≤40s | Cold start | ||
Open-phase protection | 5 | Any two phase | Third phase | Non action in 2h | Cold start |
1.0 | 0.9 | ||||
6 | 1.15 | 2 | Action in 2h | Hot(after No. 1) start |
◆Trip characteristic:
This current-time curve indicate from cold to trip time and real current and setting current multiple relationship. While running current is 1.0Xle, trip time shortened to 25%. Trip curve 3 suit for 3P load, trip curve 2 suit to 2P load, for single phase load, trip curve is between 2 and 3. For general running condition, thermal trip mechanism 3PCS bimetal need to be heated. While thermal relay used for protect single phase or DC load should in series three main contact, this moment is suitable for curve 3. Three phase to load trip current is 105%-120% to setting current.
◎Curve drawing
◆model selection and order data:
Model No. | Rated current (A) In | IEC60947-4(A) | Matched contactor model | |
aM | gG | |||
KXR28-25 | 0.1-0.16 | .25 | 2 | KXX2-09 KXX2-12 KXX2-18 KXX2-25 KXX2-32 |
0.16-0.25 | 0.5 | 2 | ||
0.25-0.4 | 1 | 2 | ||
0.4-0.63 | 1 | 2 | ||
0.63-1 | 2 | 4 | ||
1-1.6 | 2 | 4 | ||
1.25-2 | 4 | 6 | ||
1.6-2.5 | 4 | 6 | ||
2.5-4 | 6 | 10 | ||
4-6 | 8 | 16 | ||
5.5-8 | 12 | 20 | ||
7-10 | 12 | 20 | ||
9-13 | 16 | 25 | ||
12-18 | 20 | 35 | ||
17-25 | 25 | 50 | ||
KXR28-36 | 23-32 | 40 | 63 | KXX2-32 |
28-36 | 40 | 80 | ||
KXR28-93 | 23-32 | 40 | 63 | KXX2-40 KXX2-50 KXX2-65 KXX2-80 KXX2-95 |
30-40 | 40 | 100 | ||
37-50 | 63 | 100 | ||
48-65 | 63 | 100 | ||
55-70 | 80 | 125 | ||
63-80 | 80 | 125 | ||
80-930.25 | 100 | 160 |
◆Main technical data:
Item | KXR28-25 | KXR28-36 | KXR28-93 |
Current degree | 25 | 36 | 93 |
Rated isolating voltage(V) | 660 | 660 | 660 |
Open-phase protection | with | with | with |
Auto and manual reset | with | with | with |
Temperature compensation | with | with | with |
Trip indication | with | with | with |
Testing button | with | with | with |
Stop button | with | with | with |
Installation method | Plug in type, independently type | Plug in type, independently type | Plug in type, independently type |
Auxiliary contact | 1 NO+ 2 NC | 1 NO+ 2 NC | 1 NO+ 2 NC |
◎Overall installation size
◆Accessory instruction
Name | Usage |
KXR28-25 installation base | KXR28-25 as independent installation product |
KXR28-36 installation base | KXR28-36 as independent installation product |
KXR28-93 installation base | KXR28-93 as independent installation product |