KXB2-63 high breaking capacity miniature circuit breaker 3A to 63A rated working voltage 400V circuit

0.1~50.0 USD
Min. Order: 100 Piece/Pieces
Payment Terms: L/C, T/T, WU
Supply Ability: 100000PCS/PER MONTH
Place of Origin: Zhejiang

Company Profile

Location: Wenzhou, Zhejiang, China (Mainland)
Business Type: Manufacturer, Trading Company, Agent
Main Products: Distribution Box, Low Voltage Switchgear Cabinet

Product Detail

Model No.: KXB2/63
Means of Transport: Ocean, Air, Land
Type: Mini
Poles Number: 3
Brand Name: CHKX
Frequence: AC50Hz OR 60hZ
Rated working voltage: 400V or lower
Application: modern construction
Limiting degree: 3
Criteria: IEC60898, GB10963
Pole: 1P,2P,3P,4P
Rated short circuit breaking capacity:: 4000
Curve: C,D
electric life: 8000 times
Rated current: 3-40A,50-60A
Production Capacity: 100000PCS/PER MONTH
Packing: Neutral or customized
Delivery Date: 30 days or customized
Show

Product Description

KXB2-63 high breaking capacity miniature circuit breaker

Application:

KXB2-63 high breaking miniature circuit breaker have advanced structure, reliable performance, high breaking capacity, compact and elegant exterior etc features. Apply to the place with circuit of AC 50Hz or 60Hz, rated working voltage 400V or lower that it, rated current from 3A to 63A.Widely used in office building, residential for lighting, distribution system for overload, short circuit protection, also can be used for circuit infrequence converting in normal condition.

Model No. and meaning:

KXB2-63 high breaking capacity miniature circuit breaker  3A to 63A rated working voltage 400V circuit

Technical parameter:

Rated current(A)

Pole

Voltage(V)

Breaking Capacity(A)

Mechanical life()

Electric life

3-40

1P,2P

230

4000

20000

8000

2P,3P,4P

400

4000

20000

50-63

1P,2P

230

4000

20000

2P,3P,4P

400

4000

20000

Function:

1.        Short circuit protection, overload protection, control, isolation

2.        Limiting degree:3

3.        Close rapidly: Ensure reliable working in impacted load, extend circuit breaker electric life

4.        Wire connect terminal area: lower than 25A can connect several 16mm2 flexible wire, or single 25mm2 hard wire, 32A-63A can connect several 25mm2 flexible wire, or single 35mm2 hard wire

Over current tripping characteristic diagram:

Testing current(A)

Rated current(In)

Schedule time

Expect result

Initial status

Remark

1.13In

Any

T≥1h

Non trip

cold

Current rise to setting parameter in 5s

1.45In

Any

T﹤1h

Trip

cold


2.55In

In3≤2A

1s ﹤t﹤60s

Trip

cold


2.55In

In>32A

1s ﹤t﹤120s

Trip

cold


5In(C type)

Any

T≥0.1s

Non trip

cold

Close auxiliary switch connect power supply

10In(C type)

Any

T﹤0.1s

Trip

cold

Close auxiliary switch connect power supply

10In(D type)

Any

T≥0.1s

Non trip

cold

Close auxiliary switch connect power supply

14In(D type)

Any

T﹤0.1s

Trip

cold

Close auxiliary switch connect power supply

Action characteristic curve:

KXB2-63 high breaking capacity miniature circuit breaker  3A to 63A rated working voltage 400V circuit

KXB2-63 high breaking capacity miniature circuit breaker  3A to 63A rated working voltage 400V circuit

Overall and installation size:

KXB2-63 high breaking capacity miniature circuit breaker  3A to 63A rated working voltage 400V circuit

Note: Installation rail adopt JB6525TH35 type steel installation rail.


 KXM1-63 miniature circuit breaker MCCB MCB 1P-2P-3P-4P 1A to 63A

Bimetal:   Actually, it contains three metals iron, copper, cadmium, galvanized. Three metals with different coefficients of thermal expansion, bending cause thermal Pick reflect and making the breaker disconnect. This is the most import parts of the circuit breaker.  The Bimetal is the use of different materials under different breaker amperage.

Coil:  It's the important parts for the reaction of the Magnetic Trip. It's always 9 ring. As a matter of fact, the number of Coil with Different Amperage.For example, 1A reaches over 100 ring, and 63A is used to 56 ring. The Diameter Thickness is also different for Amperage.

Action Contactor(Sliver Point): It's the main point for the Reaction of Trip. Under normal conditions, keeping closed. When overload and short circuit, It will be breaking.

Arc Chute: Playing a role in destroying the arc. Generally tend to produce a large number of Moving and Static Contactor from the contactor, arc, even emerge spark.