Min. Order: | 1 Piece/Pieces |
---|---|
Payment Terms: | L/C, T/T |
Supply Ability: | 6000PCS |
Place of Origin: | Zhejiang |
Location: | Ningbo, Zhejiang, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Wind Power Generation Combined Substation, American Type Pad Mounted Substation, High Impedance Furnace Transformer, 50MVA 115KV Power Transformer |
Model No.: | 10kv 11kv 15kv 20kv 30kv 33kv 35kv 40kv |
---|---|
Means of Transport: | Ocean |
Brand Name: | sinopower |
European Type Pad Mounted Substation: | European Type Pad Mounted Substation |
American Type Pad Mounted: | Substation switchgear |
Substation: | switchgear |
Production Capacity: | 6000PCS |
Packing: | Naked Packing |
Delivery Date: | 6 months |
European Type Pad Mounted Substation
Item | Meter type | Serial No. | Measurement Scope | Accuracy | Meter State | Calibration Organization | Equipment Validity |
1 | Insulation resistance testing meter(MIT520) | ER-04-34 | 1MQ-5TQ | 5 | OK | Changzhou Measurement Co. | Mar. 9 ,2013 |
2 | Insulation resistance testing meter(MIT520/2) | ER-04-09 | 1MQ-5TQ | v | OK | Changzhou Measurement Co. | Mar. 9 ,2013 |
3 | Automatic anti-interference medium (AI-6000) | A91131A | 3-6000PF tg5: *1%+0.0004 | 1 | OK | Shanghai Electric Instrument Checking & Testing Station | Mar. 15 ,2013 |
4 | Transformer turn ratio testing meter (JYT) | 04090552 | 1〜5000 | 0.2 | OK | Changzhou Measurement Co. | Mar. 9 ,2013 |
5 | Infrared measure temperature meter (FLUKE-62) | TT-10-119 | -30oC〜500 oC | 1 | OK | Liyang Measurement Co. | Apr 18,2012 |
6 | DC resistance testing meter (JYR-40D) | 01091983 | 100uQ〜4Q | 0.2 | OK | Changzhou Measurement Co. | Mar. 9 ,2013 |
7 | DC resistance testing meter (JYR-40D) | 01091887 | 100uQ〜4Q | 0.2 | OK | Changzhou Measurement Co. | Mar. 9 ,2013 |
8 | Power-frequency capacitance voltage divider (TRF-550) | 090857 | 550 kV | 1 | OK | National HV Measurement Station | Aug. 5 ,2013 |
9 | Power-frequency excitation transformer | 090853 | / | / | OK | / | / |
(ZB-75/2*6.5) | |||||||
10 | Power-frequency capacitance voltage divider (compound power-frequency support transformer) YDTW-150 | 090862 | 150 kV | 1class | OK | National HV Measurement Station | Aug. 5 ,2013 |
11 | Power-frequency reactor (YDGK-2750/2*275) | 090854 | / | / | OK | / | / |
12 | Feebleness damp capacitance voltage divider(compound lightning impulse withstand 4000KV) FYI-1000/400 | S0927-3 | 0〜3600kV | 1 | OK | National HV Measurement Station | Aug. 5 ,2013 |
13 | Feebleness damp capacitance voltage divider(compound lightning impulse withstand 1200KV) FYI-1000/500 | S0937-5 | 0〜1200kV | 1 | OK | National HV Measurement Station | Aug. 5 ,2013 |
14 | Precision VT (HJL-110) | 0981 0982 0983 | 6KV〜110 kV/100V | 0.01 | OK | Northeast National Measurement Co. | May. 27,2013 |
15 | Precision VT (HJL-110) | 984 0986 0985 | 6KV〜110 kV/100V | 0.01 | OK | Northeast National Measurement Co. | May. 27,20131 |
16 | Precision CT (HJL-110) | 0986 0985 0984 | 5〜3000/5A | 0.01 | OK | Northeast National Measurement Co. | May. 27,2013 |
17 | Precision CT (HJL-110) | 0983 0982 0981 | 5〜3000/5A | 0.01 | OK | Northeast National Measurement Co. | May. 27,2013 |
18 | Power analyzing meter (WT3000) | 91HA17572 | 1000V, 20A | 0.02 | OK | Shanghai Measurement Co. | Jan. 18,2013 |
19 | Power analyzing meter (WT3000) | 91HA17573 | 1000V, 20A | 0.02 | OK | Shanghai Measurement Co. | Mar. 15 ,2013 |
20 | Multicenter digital partial discharge meter (TWPD-2B) | 0905XY223 | 0.1~106pC | 3 | OK | Shanghai Electric Instrument Checking & Testing Station | Nov 10, 2012 |
21 | Multicenter digital partial discharge meter (TWPD-4) | 0408XY38 | 0.1〜106pC | 3 | OK | Shanghai Electric Instrument Checking &Testing Station | Mar. 15 ,2013 |
22 | Standard pulse generator (TWPD-02) | 0908X04064 | 10〜500 pC | 1 | OK | Shanghai Electric Instrument Checking & Testing Station | Nov 10, 2012 |
23 | Sound measure meter (AWA5661) | 047090 | 24〜150dB | 1 | OK | Shanghai Measurement Co. | Apr 18,2012 |
24 | DOUBLE spectrum analyzer(W5300) | BS-02-03 | 10Hz〜1M Hz | 0.1 | OK | Shanghai Electric Instrument Checking & Testing Station | Nov 10, 2012 |
25 | Temperature Measuring Instrument | S5HB07150 | -30°C 〜500°C | 1 | OK | Jiangsu Oriental Aviation Calibration Testing CO.,LTD | Oct .14,2012 |