Low Smoke Armoured Electrical XLPE Power Cable For Underground ( 10 - 2500mm2 )

Place of Origin: Zhejiang

Company Profile

Location: Shenzhen, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: CCTV Coaxial Cable, Fire Resistant Cable, Fire Alarm System Cable

Product Detail

Model No.: YJLW02-Z 1*400

Product Description

 

Low Smoke Armoured Electrical XLPE Power Cable For Underground ( 10 - 2500mm2 ) 

 

 

Quick Detail

 

Insulation Material

XLPE

Type

High Voltage

Application

Underground

Conductor Material

Copper

Jacket

PVC

Character

waterblock

 

 

Description

 

XLPE-insulated power cables for rated voltage 110kV should perform the rules of XLPE-insulated Power 

Cable for Cable for Rated Voltage 110kV and its attachments in GB/T 11017-2002, which is equal to The 

Test Methods and Requirements of Extruded Insulation Power Cables for Voltage 30kV up to 150kV in IEC 60840:1999.

XLPE-insulated power cables for rated voltage 220kV should perform the rules of XLPE-insulated Power 

Cable for Cable for Rated Voltage 220kV and its attachments in GB/T 18890-2002, which is equal to The 

Test Methods and Requirements of Extruded Insulation Power Cables for Voltage 150kV up to 500kV in 

IEC 62067:2001.

XLPE-insulated power cables for rated voltage 500kV should perform the rules of XLPE-insulated Power 

Cable for Cable for Rated Voltage 220kV and its attachments in GB/T 22078-2008, which is equal to The 

Test Methods and Requirements of Extruded Insulation Power Cables for Voltage 150kV up to 500kV in IEC62067:2006.

XLPE-insulated power cables for rated voltage 66kV should perform The Test Methods and Requirements 

of Extruded Insulation Power Cables for Voltage 30kV up to 150kV in IEC 60840:1999.

 

 

Main Performance

 

1. The rated voltage U0/U of cables:38/66kV, 48/66kV, max. voltage Um=72.5kV;

                                 64/110kV, max. voltage Um=126kV;

                                127/220kV, max voltage Um=252kV;

                                 290/500kV, max voltage Um=550kV;

2. permissible long-term working temperature of cable conductor:90;

3. When the cable confronts short circuit within 5 seconds, the highest temperature of conductor should 

not exceed 250. When there exits line joints, the temperature of tin soldering ones should not exceed 

120, the temperature of crimping ones should not exceed 150, and the temperature of electric or gas

 welding should not exceed 250

4. When laying, the permissible bending radius should exceed 25 times of the out diameter of the cables.

   After laying, the permissible bending radius should exceed 23 times of the out diameter of the cables.

1. When laying, ambient temperature≥0(when the cable has to be laid under the ambient temperature 

below 0,it is necessary to preheat the cable above 0)