Place of Origin: | Zhejiang |
---|
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Air Cooled Water Chiller, Water Cooled Water Chiller, Industrial Water Chiller |
Model No.: | HLWW~8310M8 IM |
---|
CE Proved 8310 KW Water Cooled Chilled Water Industrial Chiller For Industry And Commercial Use
Product Detail:
1. Widely used in industry fields such as leather, plastic injection, medicine, chemical, hydraulic system,
leaser, printing, etc.
2. Water-cooled with higher COP and EER.
3. Cooling capacity: 8310KW.
4. Inlet chilled water temperature: 17 degrees.
Outlet chilled water temperature: 12 degrees.
5. Inlet cooling water temperature: 5~20 degrees.
6. Adopting Semi-Hermetic screw type Hanbell compressor,
High efficient shell & tube type evaporator.
7. Refrigerant: R22 or R407C, R134A, R410A (optional).
8. CE approved.
Product Application:
Golden brand industrial chiller may be widely used in the field of leather, plastic injection, surface treatment,
medicine, chemical, hydraulic system, leaser, shoe-making, electronic, print etc
Matching Equipment:
Water cooling chiller shall be compacted with the cooling tower, water pump, water tank etc. Water cooled
series with higher COP and EER than air cooled chillers no matter the ambient temperature is. This machine
is in elegant appearance by using electrostatic spray powder shell and European design. If needed, we could
provide with the cooling tower, water pump, water tank etc to compact the chillers.
Service:
All our Golden chillers have one year of free maintenance period starting from the date of delivery. The
damaged part can be replaced free of charge if it is because of quality reasons, not damaged due to manual
wrong operation.
Product Packing:
Standard wooden frame packaging, also could meet the requirement of clients.
Packed in air bubble film inside, then in plywood case outside, or wooden package, wooden crate.
Product Parameter:
Model HLWW | 8310M8 IM | |
Rated Cooling Capacity | ×1000kcal/h | 7145.7 |
KW | 8310 | |
USRT | 2362.9 | |
Input Power | KW | 1445.6 |
Refrigerant | R407C | |
Power Supply | 3φ-380V-50HZ | |
Safety Protection | Phase reversion protection, | |
Phase lack protection, | ||
Overload current protection, | ||
Discharge air temp. protection, | ||
Low & High pressure protection, | ||
Low temp. protection, Water flow protection, | ||
Number of Refrigeration Circuit | 8 | |
Refrigerant Charge (Kg) | 1264 | |
Dia.of Pipe to Condenser (Modular) (inch) | 5" | |
Water Side Max Pressure (Modular) (MPa) | 1 | |
Condenser Water Pressure drop (Modular) (kPa) | 68 | |
Cooling Water Flow (m3/h) | 1677.7 | |
Dia.of Pipe to Evaporator (Modular) (inch) | 5" | |
Water Side Max Pressure (Modular) (MPa) | 1 | |
Evaporator Water Pressure Drop (Modular) (kPa) | 69 | |
Chilled Water Flow (m3/h) | 1429.1 | |
Running Noise (Modular) dB(A) | 75 | |
Total weight (Kg) | 27200 |
Product Show:
&nb