Place of Origin: | Zhejiang |
---|
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | AC Frequency Drives, Low Voltage Variable Frequency Drive, Solar Variable Frequency Drive |
Model No.: | VT6KS(10KS) |
---|
240VDC Battery Voltage High Frequency Online UPS Single Phase 10KVA
Quick Detail:
Specifications:
Model |
VT6K |
VT6KS |
VT10K |
VT10KS |
||
Rating |
6KVA/4800W |
10KVA/8000W |
||||
Input |
Input system |
Single phase & earth ground |
||||
Voltage range |
(120±5)VAC~ (275±5)VAC |
|||||
Power factor |
≥0.99 |
|||||
Voltage range of bypass |
(60±5)VAC~ (300±5)VAC (default: 60VAC~300VAC |
|||||
Output |
Output system |
Single phase & earth ground |
||||
Rated voltage |
220VAC |
|||||
Power factor |
0.8 |
|||||
Voltage precision |
±1% |
|||||
Output frequency |
Normal mode |
1.The output frequency synchronizes with the input frequency |
||||
Battery mode |
||||||
Inverter overload capacity |
105%±5%<Load≤125%±5% 60s transfer to bypass |
|||||
Transfer time |
0ms (Normal mode←→ Battery mode) |
|||||
<4ms (Normal mode←→Bypass mode) |
||||||
Crest factor |
3:1 |
|||||
Battery |
Batteries voltage |
192VDC |
||||
Battery quantity |
16 |
|||||
Battery Type |
Sealed maintenance-free lead –acid battery |
|||||
Backup Time (25) |
Full load≥5min (Standard) |
|||||
Charge current |
Standard 1A |
Long 6.5A |
||||
Note1: Output voltage can be set: 200V/208V/220V/230V/240V. |
Zero power switch delay: When the utility power fails, UPS will automatically switch from AC mode to battery mode with no delay, which ensures stable power supply of operating system.
Active Load Management: This technology allows the UPS to be set up at a fixed 50Hz or 60Hz output, while it also can intelligently monitor power usage and automatically sheds and reconnects loads in order to prevent generator overload.
Sufficient Expansion Slots: The pre-allocated smart slots enable flexibility in choice of USB cards,AS400 cards, CMC monitoring cards, SNMP cards, RS485 cards and EMD environment monitoring cards.
The load power factor is 0.8: it adapts the features of most current electric equipment and elevates the load-bearing capacity of the machines.
Generator Supportable:The wide range of input voltage and frequency can effectively separate the harmful electric wave produces by the generators and provide safe and reliable power supply.