Place of Origin: | Zhejiang |
---|
Location: | Guangzhou, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Programming Logic Controller, Micro PLC Controller, Direct Logic PLC |
Model No.: | UN277-0AA22-0XA0 |
---|
EM 277 PROFIBUS-DP Module is an intelligent expansion module which connects S7-200 CPU to PROFIBUS-DP net by Serial I/O
Detail description
As a DP substation, EM277 Module receives different I/O configurations from main station, sends and receives different quantites Data, it is convenient for customer to revise the transferred data to suit for the request of practical application.
Advantage
1. Support S7-200 PLC( such as CPU 224, 224XP)
2. Support S7-300 CPU with DP main station function
3. RS-485 communication and self suit for 9.6kbps-12mbps
4. Max. support 99 DP substations
5. RS-485 port with Photoelectric isolation, over-current protection
6. Power supply with reverse connection protection and surge absorption.
Specification
Model |
EM277 PROFIBUS-DP Module |
Description |
Be used in distributed I/O system with PROFIBUS-DP interface |
Module feature |
|
Port |
1 |
Port Type |
RS-485 |
Protocol |
PROFIBUS-DP |
PROFIBUS-DP Speed |
9.6, 19.2, 45.45, 93.75, 187.5 and 500Kbps |
Net Ability |
|
Sub-station address setting |
0 to 99(setting by rotary switch) |
Max Sub-station per Net section |
32 |
Max Sub-station per Net |
126, but just 99 EM277 Sub-station |
Cable Length |
|
Below 93.75kbps |
1200 meters |
187.5kbps |
1000 meters |
500kbps |
400 meters |
1-1.5Mbps |
200 meters |
3-12Mbps |
100 meters |
24V DC input power |
|
Voltage range |
20.4-28.8V DC |
MAX. Current consume (24VDC) |
70mA |
Isolation( Input power with Logic circuit) |
500V |
Power Supply consume |
|
5V DC consume on BUS |
150mA |
Dimension (length x width x hight) |
71 x 80 x 62 |