CT PT Analyzer Technical Index: 1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 2 Power supply: AC220V±10%,50Hz/60Hz±10% 3 Power output: 0.1~180V (AC) 4 Current output: 0.001~5A(RMS) 5 Power output:300VA 6 Maximum knee voltage measurement:45kv 7 Current measurement: Range:0~10A (automatically change range in 0.1/0.4/2/10A) Error <±0.1%+0.01%FS 8 Voltage measurement: Range:0~200 V (automatically change range in 1V/10V/70V/200V) Error < ±0.1%+0.01%FS 9 Turns ratio measurement: Range :1~35000, 1~2000 error<0.05% 2000~5000 error>0.1% 5000~35000 error<0.2% 10 Phase measurement: error:±2min,resolution:0.01min 11 Coil resistance measurement: Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution:0.1mΩ 12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree 13 CT Secondary burden: Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm 14 PT Secondary burden: Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm 15 PT ratio measurement: Range :1~35000, 1~5000 error<0.2% 5000~35000 error<0.5% 16 Saved data groups:>1000groups 17 Work condition: Temperature:-10℃~50℃, moist:≤90% 18 Size: 485mm×356mm×183mm 19 Weight: <15Kg
|