user login

4 Phase AC Protection Relay Test Set , 10.4 Inch LCD Screen K5030

Place of Origin: Zhejiang

Company Profile

Location: Shenzhen, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: Protection Relay Testing, Relay Test Set, Relay Test System

Product Detail

Model No.: KS-3000

Product Description

4-Phase AC Protection Relay Test Set , 10.4 Inch LCD Screen K5030

 

Relay protection test devices
1.Easy test
2.operation menu, Simple operation
3.Nominal input voltage:220VAC
4.Power:1200VA

 

Latest Technology make you stand ahead!

 

K50 series relay tester with latest technology, extremely design for your now and funture use, with power PC software, unique features and functions helps you stand ahead of your competitors!

 1. Adopts 10.4 large LCD screen, and provided with VGA video interface, making it available to connect to projector for training;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A(Poleless and adjustable);
5. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
6. Function of transducer and energy meter testing (optional function);
7. Adopt Smart and stable Window CE embedded system. Windows has the advantage of small application program with fast speed, which overcomes the problem of bad stability, easy-damage hardware, and virus of Windows 98/2000/XP;
8. Use high-speed CF card as the storage, more stable, anti-shock compared with ordinary hardware, so works more reliable.
 
 Technical Data of K5030
 

 

Post Buying Request

Voltage generators

Setting

Range

4-phase AC (L-N)

4 x 0 ... 130 V

2-phase AC (L-L)

2 x 0 ... 260 V

Power

4-phase AC (L-N)

4 x 70VA, at 0 ... 130V

2-phase AC (L-L)

2 x 110VA, at 0 ... 260V

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-130V

<0.04% reading + 0.01% range typical at 0-130V

Resolution

1mV

Current generators

Setting

Range

3-phase AC (L-N)

3 x 0 ... 30 A

1-phase AC (2L-N)

1 x 0 ... 60 A

1-phase AC (3L-N)

1 x 0 ... 90 A

Power

3-phase AC (L-N)

3x 250VA , at ....30A

1-phase AC (2L-N)

1x 840VA, at ….60A

1-phase AC (3L-N)

1 x 1000 VA, at ...90A(Max)

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-30A

<0.02% reading + 0.01% range typical at 0-30A

Resolution

1mA

Generators, general