Place of Origin: | Zhejiang |
---|
Location: | Guangzhou, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Silent Diesel Generators, Cummins Diesel Generator, Portable Diesel Generator |
Model No.: | Cummins 20KVA~300KVA |
---|
1.Frequency 60HZ, 1800RPM
2.Rating voltage 208V/120V
3.1100KW/1375KVA
4.Model of Connection: 3 phase 4 lines
1320KW / 1650KVA MTU Diesel Generating Sets , Water-cooled
Standard Features: | |||
Frequency 50HZ, 1500RPM, Rating voltage 380V/220V, 400V/230V | |||
Frequency 60HZ, 1800RPM, Rating voltage 208V/120V, 220V/127V, 480V/277V | |||
Power Factor 0.8(lagging) | |||
Protection Standard: IP21-IP23 | |||
Model of Connection: 3 phase 4 lines | |||
Insulation Grade: H | |||
Frequency Drop(%): ≤ 0.5 | |||
Transient state frequency deviation(%):(advertised power ) +10-7 | |||
Frequency Recovery Time(S): ≤ 3 | |||
Voltage Recovery Time(S): ≤4 | |||
Waveform Distortion(%): ≤5 | |||
Voltage Regulation: +_1.0% |
Descrptions:
Victory MTU Series Diesel Generator set adopts Germany brand MTU diesel engine, which is made by Shanxi Diesel Engine Industries Corporation LTD. The features of MTU series diesel generating sets:
A. Maintenance maintenance-friendly: Water-cooled 4-stroke 90 ° V-cylinder arrangement, the turbo in the cold, wet can be used for cylinder, a cylinder, dry exhaust Manifold, easy to maintain;
B. Intelligence operation: The use of advanced MDEC / ADEC electronic management system can provide accurate digital electronic speed control function, the key body parts Set up data acquisition, failure to achieve self-diagnosis and automatic, intelligent unit operation, CAN bus technology;
C. High operating reliability: The three-part structure of aluminum Detroit Pistons top the use of wear-resistant cast iron ring, the valve seat Ring structure, long life, Detroit injection cooling, an effective solution to the cooling cooling, more reliable operation of generating units;
D. Energy conservation and environmental protection: A unique electronically controlled fuel pump monomer, with cylinder direct injection, is superior to the German TA Luft emissions standards, electronic intelligence management, Lower fuel consumption, the first to break through 200 g / kWh bottlenecks;
E. Excellent performance: Operational stability and vibration of small, fuel consumption rates, oil consumption rate is low and long operating life, overhaul a long time and low noise.
Rating Definations
Continuous Power
These ratings are applicable for supplying continuous electrical power (at variable load) in Lieu of commercially purchased power. this is no limitation to the annual hours of operation and this model can supply 1% overload for 1 hour in 12 hours
Standby Power
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defind in ISO8528-3) at 27
GENERATOR SETS POWERED BY MTU ENGINE
MAIN SPECIFICATION OF GENERATOR SETS
GENSET MODEL |
V1210MTU | V1452MTU | V1650MTU (extrinsik cycle) | V1936MTU | V1452MTU1 | V1760MTU | V1980MTU |
Prime Power |
1100KW /1375KVA |
1320KW /1650KVA |
1500KW /1875KVA |
1760KW /2200KVA |
1320KW /1650KVA |
1600KW /2000KVA |
1800KW /2250KVA |
Standby Power |
1210KW /1512KVA |
1452KW /1815KVA |
1650KW |