Outdoor Gang Isolator Switch

  1. Rated voltage:11/33KV
  2. Rated current:400/600A
  3. Standard:IEC60964:1996/IEC62271-102:2002

 

 

Description:

 

Outdoor AC Gang isolator switch 11kv/400A-33kv/600A used in 3 phase AC 50/60Hz power circuit, it is used as switching on and switching off at the voltage with no load. It apply to IEC standard. IEC60964: 1996, IEC62271-102: 2002.

 

 

Technical Specification

 

Type

Rated
voltage
(KV)

Rated
current
(A)

4S Heat
steady
e. c. A

Impulse
withstand
voltage A

Impulse voltage

Power frequency
withstand voltage

To earth
(KV )

Across the
isolating
distance (KV)

To earth
(KV )

Across the
isolating
distance(KV)

RH-B

11

400

12500

31500

75

95

38

42

33

600

12500

31500

170

195

70

80

 

Altitude:1000 to 3000m.

Ambient temperature:-30 celsius to +40celsius

The relative humidity of air:monthly humidity not more than 90%,daily humidity not more than 95%.

Wind pressure:not more than 700Pa( wind speed is 34m/s).

Amplitude:earthquake degree 8

Environmental pollution degree:degree III

 

 