Three phase power supply Lightning Protection box

Min. Order: 1 Set/Sets
Payment Terms: T/T
Supply Ability: 200
Place of Origin: Shaanxi

Company Profile

Location: Xi'an, Shaanxi, China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: KNFX380-40
Means of Transport: Ocean, Air, Land
Brand Name: chinastarwin
Protection level: IP20
Nominal voltage: 380V AC
Max continuous operating voltage: 440V AC
Nominal current: 80A
Nominal discharge current(8/20μs): 40KA
Max discharge current(8/20μs): 80KA
Working frequency: 47~63Hz
Interface type: Parallel
Connection mode: Crimping terminal
Protected mode: L1/L2/L3 to N,N to PE
Production Capacity: 200
Packing: wooden case
Delivery Date: 1 week
Show

Product Description

KNFX380-40 Three Phase Power Supply Lightning Protection Box

 

Three phase power supply lightning protection box is suitable for three-phase power supply system, protection 

class C power protection products belongs to SPD, parallel connection in the power supply system, To prevent 

the outside (lightning, electromagnetic interference etc.) or the system (system of stretch closing effect, inductive

and capacitive load start and stop etc.) induced by pulsed surge and instantaneous over voltage damage to the 

power supply system equipment.

This product has large discharge reserve energy, up to a maximum of 80kA (8/20μs), a low level of protection, 

safe and reliable, reasonable structure, convenient installation, and design a Kevin connection mode, can guarantee

the best protective effects to the power system.

 

 

Working Principle

This product uses the popular protection devices switch type of protection components(which presents a high 

 impedance in the absence of surge and overvoltage once the selected surge and overvoltage protection devices 

 reached the value, and the emergence of a low impedance) and the limit of the most commonly(which presents 

 high impedance, in the absence of surge and overvoltage when the selected surge and overvoltage protection 

 devices once reached values, and started and will increase with the surge and overvoltage, the impedance will 

 continue to decrease) used on the nonlinear characteristics of surge and overvoltage when working, coupled 

 with its fast corresponding characteristics will surge, timely discharge to the earth, and the voltage clamp in the 

 equipment can withstand the voltage range.

 

 

Work Environment

·Working temperature: -40℃~ +80℃

·Relative humidity:5% ~ 95%

·Atmospheric pressure:74.8kPa ~ 106kPa

 

 

Technical Parameters

Type


KNFX380-40

Nominal voltage

UN

380V AC

Max continuous operating voltage

Uc

440V AC

Nominal current

IN

80A

Nominal discharge current(8/20μs)

In

40KA

Max discharge current(8/20μs)

Imax

80KA

Limit the voltage(8/20μs,25KA)

Up

≦1.5KV

Working frequency

fG

47~63Hz

Response time

tA

≦25ns

Protected mode

              L1/L2/L3 to N,N to PE

 

Interface type


Parallel

 

Connection mode


Crimping terminal

Case material


265mm*165mm*65mm

Remote communication alarm

(BNC interface, analog switch output signal )


Normal is normally closed, failure is always open, switch output

 

 

Installation and Maintenance

1.The installation mode of the product is wall mount, and is installed with the corresponding accessories, during 

   the actual installation according to the concrete circumstance to installation.

2.This product uses the black aluminum alloy shell, before the installation, check if the products and accessories 

   are complete and fully intact. Fix The products ,according to the wiring diagram of the power line and the 

   ground wire connected properly, check after electrifying, normal work, the indicator light  is  normal green.

3.For the normal work of the lighting protection gate, grounding is very important, the grounding wire cross-

   sectional area is no less than 16mm ², and as short as possible.

4.The product needs no special maintenance, but it is on position for a long- term period, so we should assign 

   someone to inspect regularly, especially in the season of thunderstorms. Once stuck by lightning, inspect it 

   immediately.

5.This product has set up a working indicating light, ground light, malfunction indicator light and remote alarm. 

  When working properly, the working indicator light green light, ground indicator light green light, when the 

  protection device of each phase after a fault occurs, the fault indicator light red light, at the same time, remote 

  signal alarm output ports normally opened switch quantity signal.

6.When working, the internal components is with 380V alternating current, must Caution!

 