user login

Portable Energy Meter Test Equipment , High Voltage Single Phase Calibrator

Place of Origin: Zhejiang

Company Profile

Location: Guangzhou, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: Energy Meter Test Bench, Single Phase Energy Meter Test Bench , Three Phase Meter Test Bench

Product Detail

Model No.: KE8800

Product Description

Portable Energy Meter Test Equipment , High Voltage Single Phase Calibrator

 

  1. Name: Portable energy meter calibrator, portable meter test equipment
  2. Phase: Single Phase
  3. Accuracy Class:   0.1%
  4. Usage: Auto Electric meter test and calibration
  5. Power: Electronic
  6. Testing mode: active power,  reactive power
  7. Voltage Output: 0V – 300V
  8. Current Output: 1mA – 120A
  9. Operating Temperature: -10°C -- +40°C
  10. With self-checking function

 
Energy Meter Test Equipment, High Voltage Single Phase Portable Calibrator
 
KE8800 portable single phase calibrator used to test single phase energy meter. Adopt mature signal synthetic and power amplifier technology. High voltage and current output. Widely used in lab and field. 
 
Character:

  • Meter under testing: 1P2W
  • Testing mode: active power,  reactive power
  • Test 3pcs meter synchronously 
  • Starting test and creeping test
  • Reference standard and power source integrated,  easy to carry.   
  • Measuring mechanical meter and electric meter 
  • Operating by manual keyboard or PC
  • With shortcut key of normal test point,  speed up testing  
  • Internal large capacity storage device for mass memory
  • Local checking the testing result
  • Overload,  short circuit,  open circuit protection
  • With self-checking function

 
Technical Data:

 

Post Buying Request

Voltage

Test voltage output (Phase-Neutral)

0V – 300V

Power of the voltage output

Max. 30VA

Resolution

0.01%

Accuracy

0.1%

Stability

0.02%/120s

Distortion factor

< 0.3% for linear resistance load

Current

Test current output

1mA – 120A 

Power of the current output

Max. 100VA

Resolution

0.01%

Accuracy

0.1%

Stability

0.02%/120s

Distortion factor

< 0.3% for linear resistance load

Phase angle

Range

0 -- 360°

Resolution