user login

66KV Electrical Power Transformers

Place of Origin: Zhejiang

Company Profile

Location: Shenzhen, Guangdong, China (Mainland)
Business Type: Manufacturer
Main Products: Electrical Power Transformers, AC Power Transformers, Oil Immersed Power Transformer

Product Detail

Model No.: SF, SFZ, SZF, SFSZ, SZZ

Product Description

 

66KV 10MVA 3 Phase Electrical Power Transformers For Station / Laboratory

 

Quick Detail:

 

1. Rated Voltage: 66KV

2. Rated Capacity: 10000KVA

3. Phase: Three Phase / Single Phase

4. Cooling Type: ONAN / ONAF

5. Frequency: 50Hz / 60Hz

 

 

Technical Parameter Specifications:

 

Rated Voltage

66KV

Rated Capacity

10000KVA

Cooling Type

ONAN/ONAF

Winding Type

Double winding / Three winding / Toroidal

Phase

Three Phase / Single Phase

Type

Core Type / Shell Type 

Winding Material

Copper

Frequency

50HZ / 60HZ

 

Type:

S9-10000/66

Voltage ratio:

66±2x2.5%

63±2x2.5%

Low voltage:

6.3; 6.6; 10.5; 11

Connection symbol:

YNd11

No Load Loss:

11.36kW

Load Loss:

50.4kW

Short Circuit Impedance

9%

Total weight (T)

22.7

Dimension(mm)

4200*3800*5160mm

Track center Spacing (mm)

1475

 

 

Description:

 

The 66KV transformer is based upon world-wide advanced technology and also incorporates the experiences of internationally leading transformer companies as well as our own long-term experiences. Low loss, low partial discharge and high short circuit withstand capability series transformers are achieved through innovation and optimization. Our transformer conform entirely with latest national standard GB1094.1~2-1996, GB1094.3-2003, GB1094.5-2003 and international standard IEC-76. Outstanding features as follows:

1. Low loss, and significantly energy-saving. The average no-load loss is 35% lower than prescribed by National Standard GB/T 6451-2008.

2. The core laminations are made up from high-quality cold-rolled grain-oriented silicon steel sheets with chamfered joints and without punched holes, and are stacked without the upper yoke sheets in place, so that they are effectively improved no-load upper together with lower frame.

3. Zigzag directed flow of oil are provided within the windings, so that all parts of the windings can be cooled more evenly.

4. The regulating winding is a separate winding which apart from the high voltage main winding.

5. The windings of one phase are assembled into an integral phase block before placing into the core.

Post Buying Request