Min. Order: | 1 Set/Sets |
---|---|
Trade Term: | FOB |
Payment Terms: | L/C, T/T, WU |
Supply Ability: | 20set/month |
Place of Origin: | Hebei |
Location: | Baoding, Hebei, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Resistor, Power Meter, Transformer, Arc Suppression Coil , Switchgear |
Model No.: | MRD-KYN28-12 |
---|---|
Means of Transport: | Ocean |
Brand Name: | MINGRUI |
Production Capacity: | 20set/month |
Packing: | wooden case |
Delivery Date: | 35-45days against deposit or L/C |
1. Operating Conditions
Ambient temperature: max. to 40 centigrade, min. to -10 centigrade
Altitude: not exceeding 1000m
Relative humidity: daily average less than 95%, monthly less than 90%
Earthquake intensity: less than 8 magnitudes
Installation site: without fire risk, explosion hazard, heavy pollution, chemical corrosion and violent vibration
Note: Special condition and requirements, consult with the manufacturer
2. Characteristic
Metal-clad and partition completely, effectively prevent faults spreading
The low voltage section is completely separated from the high voltage sections
Enclosure protection degree is IP4X, protect against electric shock and ingress of solid foreign bodies
Simple but effective interlocking prevents mal-operation
Space is provided for multiple cable connections. Installation and maintenance is convenient
Withdrawble part of the same design are mutually interchangeable, an exchange of VCB is very simple.
3. Technical Data
Name | Unit | Data | |
Rated voltage | kV | 3.6, 7.2, 12 | |
Rated insulation level | Rated power-frequency withstand voltage(1min)
| kV | 42 |
Rated lightning impulse withstand voltage | kV | 75 | |
Rated frequency | Hz | 50 | |
Main busbar rated current | A | 630, 1250, 1600, 2000, 2500, 3150 | |
Branch busbar rated current | A | 630, 1250, 1600, 2000, 2500, 3150 | |
Rated short-time withstand current(rms), 4s | kA | 16,20, 25, 31.5, 40, 50 | |
Rated peak withstand current (peak) | kA | 40, 50, 63, 80, 100, 125 | |
Enclosure protection level | The enclosure is IP4X, it is IP2X when compartment and circuit breaker room is open | ||
Weight | 700-1200kg |
4. Outline dimensions & weight
Height (mm) | 2300 | |
Width (mm) | Branch busbar rated current up to 1250A | 800 |
Branch busbar rated current down to 1600A | 1000 | |
Depth (mm) | Front maintenance Double-face maintenance | 1500 1660 |
Weight (kg) | 700-1200 |
5. Construction
The basic structure of the switchgear panel comprises the panel itself and withdrawable part.
The panel is constructed by bolting together. Enclosure and internal partition are of anticorrosive steel sheets. The panel consists of four separate compartments, that is truck compartment, busbar compartment, cable compartment, low-voltage maintenance type, double-face maintenance type. Withdrawable part can be classified by function to:
VCB truck
PT truck
Disconnect truck
Metering truck
HV fuse truck etc.
6. Ordering instructions
Please specify the following information when ordering
The main wiring scheme, single wire system diagram, pareto chart and layout plan
The quadratic function diagram, terminal diagram
Components inside the switchgear model number, specifications and quantities
Electrical equipment summary table
Span length and height dimensions if bus structure is needed
If the equipment needs to be used in special environment, place advise