user login

Transformer neutral discharging gap

100.0~1000.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: L/C, T/T, WU
Supply Ability: 1000sets/month
Place of Origin: Hebei

Company Profile

Location: Baoding, Hebei, China (Mainland)
Business Type: Manufacturer
Main Products: Resistor, Power Meter, Transformer, Arc Suppression Coil , Switchgear

Product Detail

Model No.: MRD-NP
Means of Transport: Ocean, Air, Land
Brand Name: MINGRUI
Production Capacity: 1000sets/month
Packing: Wooden case or according to customers' request
Delivery Date: 20days against deposit
Show

Product Description

1.       Operation conditions

Applicable for indoor and outdoor

Ambient temperature: -50 to +55 Celsius

Altitude: 1500m, if exceeds, we can produce as per specific details

Max earthquake intensity: 8 grades

Frequency: 50Hz and 60Hz system

Max wind pressure: 700Pa

 

2.       Typical technical data

 

 

 

 

 

Product Model No.

MRD-NP-110

MRD-NP-220

Transformer Rated Voltage KV

110

220

Transformer Neutral Withstanding Voltage

Lightning   Impulse Withstand Voltage KV  (peak   value)

250

450

1min   Power-Frequency Withstand Voltage KV (effective value)

95

200

Disconnecting Switch

Model No.

GW13-72.5W

GW13-126W

Rated   Current  A

630

Operation Mode

CS17 (Manual) or CJ6 (Motor-drive)

Lightning Arrestor

Model No.

Y1.5W-72/168

Y1.5W-144/320

Rated   Voltage  KV

(effective   value)

72

144

Continuous   Operation Voltage  KV

(effective   value)

58

116

8/20µs Lightning   Impulse Residual Voltage  KV

(peak value)

≤186

≤320

Discharging Gap

Shape

Clavate or Spherical

Discharge   Distance mm

90-135

250-320

Power-frequency   Discharging Voltage KV (effective value)

50-63

100-127

Current Transformer

Type

Epoxy Resin-Totally Enclosed-Pillar Type

CT Ratio

100/5, 200/5, 300/5, 400/5, 500/5, 600/5

 

 

3.       Ordering instructions

 

Please inform us the following data before place the order

 

Transformer insulation level and rated capacity

 

The precision, ratio and capacity of Discharging gap protection CT

 

Rated current of the isolating switch and the operating mechanism of the operating mode

 

Rated voltage and lightning residual pressure of Zinc oxide lightning arrester

 

Operating environment (indoor or outdoor, pollution grade and altitude etc.)

 

Installation method: pre-built concrete pole pillar by user or a whole set of over-ground mounting bracket and accessories matching supplied with the device

Project name, product model, product quantity and delivery time

 

Other special requirements beyond the above stipulations need to negotiate before place the order

 

 


Post Buying Request