        GDVA-404 Current Transformer CT  PT Testing Equipment 

 

                                                                  

 

 

 

 

 

Product Description

 I Introduction

 

GDVA-404 Current Transformer CT  PT Testing Equipment is performing excitation, ratio and phase error, polarity, secondary loop burden and coil resistance on current and voltage transformer. The instrument provides fully automatic testing and calibration for all types of low leakage flux current transformer and inductive voltage transformer. The maximum knee point voltage of sample CT could be reached 8.4kv.


The standards support by  CTPT Transformer testing equipment include IEC60044-1, IEC60044-2, IEC60044-6 and C57.13

 

 

II Technical  Parameter

 

 

ModelGDVA-404  CT  PT Transformer Testing Equipment 
Test standardsIEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
Power supplyAC220V±10%,50Hz/60Hz±10%
Power output0.1~125V (AC)
Current output0.001~5A(RMS)
Power output300VA
Maximum knee voltage measurement45kv
Current measurementRange:0~10A (automatically change range in 0.1/0.4/2/10A)           
Error <±0.1%+0.01%FS
Voltage measurementRange:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
Turns ratio measurementRange :1~30000
1~2000 error<0.05%
2000~5000 error>0.1%
5000~30000 error<0.2%
Phase measurementerror:±2min,resolution:0.01min
Coil resistance measurementRange:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS
Maximum resolution:0.1mΩ
Temperature measurement   -50~100 Celsius degree, error<3 Celsius degree
CT Secondary burdenRange 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
PT Secondary burdenRange 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
PT ratio measurementRange :1~30000
1~5000 error<0.2%
5000~30000 error<0.5%
Saved data groups>1000groups
Work conditionTemperature:-10ºC~50ºC, moist:≤90%
Size485mm×356mm×183mm
Weight<15Kg

 

 