GDYJ-501 Transformer Oil Dielectric Test Equipment
Reference Standard:
1. GB-86 Insulating Oil Dielectric Strength Testing Method
Characteristics:
1. Lcd display the test procedure and test result.
2. All the human interaction operations is completed through the rotating mouse.
3. Easy for customers to measure the breakdown voltage of all kinds of oil.
4. Built-in micro printer which can print the test result.
5. Rs232 allowed pc connecting work.
6. Good performance at stability an anti-noise.
Functions:
1.
Breakdown test of user-defined
2. Proof
test
3.
Calibration interface for customers
4.
Unloading data to PC and making word report automatically.
5. Result
print
Technical Parameter:
No | Name | Parameter | Remark |
1 | Rated Power Supply | AC 220V±10% 50/60Hz | |
2 | Output Voltage | AC 0~80KV/AC 0~100KV | |
3 | Rate of Voltage Rise | 2KV/s±10% | |
4 | Measuring Precision | Grade 3 | |
5 | Times | 1~9 times | |
6 | Mixing Time | 0~99 seconds | |
7 | Placing Time | 0~9mins and 59 senconds | |
8 | Data Storage | 100 groups | |
9 | Voltage Limit Setting for proof test | 20KV~70KV | |
10 | Hold time for proof test | 1~10mins | |
11 | Working Temperature | 5~40°c | |
12 | Relative Humidity | ≤80% RH | |
13 | Dimension | 420×380×410mm | |
14 | Weight | 28 kg |