ITEM:LY1-D20Surge Protective Device
LY1-D20 is suitable for TN-S/TN-C-S/TT/IT etc . power supply system of AC50/60 Hz, ≤ 380V,installed on the joint of LPZ1 or LPZ2 and LPZ3,it's designedaccording with IEC61643-1/GB18802.1,it adopts 3.55mm standard rail,there is afailure release mounted on the module of surge protective device.When the SPDfails in breakdown for over-heat and over-current,the failure release will helpelectric device seperate from power system and give the indication signal,greenmeans normal,red means abnormal,it's also could be replaced for the module whenhas operating voltage.
Products features
1.Could be replaced for the module not need power cut
2.Maximum current of endurethe lighing stoke 10kA (8/20μs)
3.Time of response <25ns
4.The color of visible window shows operating status,green means normal,redmeans abnormal
Main technical parameters:
Techinical parameters | Model LY1-D20 |
Rated operatingvoltage Un(V~) | | | 220V | 380V |
Maximumcontinuous operating voltage Uc | | | 320V | 385V |
Voltageprotection level up(V~) KV | | | ≤1.2 | ≤1.5 |
Nominaldischarge current In(8/20μs)KA | | 10 |
Maximumdischarge current Imax(8/20μs)KA | | 20 |
Responsetimes | <25 |
Teststandard | GB18802.1 IEC61643-1 |
The crosssection of L/N line | 6 |
The crosssection of PE line | 16 |
Fuse ofswitch(A) | 10A,16A | 16A,25A |
Operatingenvironment°C | -40°C~85°C |
Relativehumudity(25°C) | ≤95% |
Installation | Standard rail 35mm |
Material ofouter covering | Fiberglass reinforced plastic |