Aluminum Conductor Steel Reinforced bare wire
Type of conductor:
1 AAC:All Aluminium Conductors
ASC:Aluminium Stranded Conductors
2 AAAC:All Aluminium Alloy Conductors
AASC:Aliminium Alloy Stranded Conductors
3 ACSR:Aluminium Conductor Steel Reinforced
4 ACSR/AW
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
mm2 | No. | mm | mm | kg/km | kN | Ω/km |
16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
150 | 147.1 | 37 | 2.25 | 15.8 | 405.7 | 26.48 | 0.196 |
185 | 181.6 | 37 | 2.5 | 17.5 | 500.9 | 31.78 | 0.1588 |
240 | 242.5 | 61 | 2.25 | 20.3 | 671.1 | 43.66 | 0.1193 |
300 | 299.4 | 61 | 2.5 | 22.5 | 828.5 | 52.4 | 0.0966 |
ACSR Technical Characteristics Based on Standard BS 215-2
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area of aluminium | Total sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
Al | Steel |
mm2 | No./mm | mm2 | mm2 | mm | kg/km | Ω/km | kN |
RABBIT | 50 | 6/3.35 | 1/3.35 | 52.88 | 61.7 | 10.05 | 214 | 0.5426 | 18.35 |
DOG | 100 | 6/4.72 | 7/1.57 | 105 | 118.5 | 14.15 | 394 | 0.2733 | 32.7 |
WOLF | 150 | 30/2.59 | 7/2.59 | 158.1 | 194.9 | 18.13 | 726 | 0.1828 | 69.2 |
DINGO | 150 | 18/3.35 | 1/3.35 | 158.7 | 167.5 | 16.75 | 506 | 0.1815 | 35.7 |
LYNX | 175 | 30/2.79 | 7/2.79 | 183.4 | 226.2 | 19.53 | 842 | 0.1576 | 79.8 |
ZEBRA | 400 | 54/3.18 | 7/3.18 | 428.9 | 484.5 | 28.62 | 1621 | 0.0674 | 131.9 |
AAAC Technical Characteristics Based on Standard BS 3242
Code name | Nominal aluminium area | Stranding and wire diameter | Sectional area | Approx. overall diameter | Approx. mass | Calculated D.C. resistance at 20oC | Calculated breaking load |
mm2 | No./mm | mm2 | mm | kg/km | Ω/km | kN |
ALMOND | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 1.094 | 8.44 |
CEDAR | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 0.9281 | 9.94 |
FIR | 40 | 7/2.95 | 47.84 | 8.85 | 131 | 0.688 | 13.4 |
HAZEL | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 0.5498 | 16.8 |
OAK | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 0.2769 | 33.3 |
ASH | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 0.183 | 50.65 |
ELM | 175 | 19/3.76 | 211 | 18.8 | 580 | 0.1568 | 59.1 |
UPAS | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 0.09155 | 101.5 |
Overhead Cable Cable Conductor Conductor Bare Fiber Overhead Showers Overhead Crane More>>
Find more related products in following catalogs on Hisupplier.com
Electronic & Electrical >> Wires, Cables & Cable Assemblies >> Bare Wires
2.8M3 4M3 5M3 6M 6M3 7M3 8M 10M 12.5M 14M 16M 18M 20M 25M Guy Alumoweld
3M3
Guy Alumoweld Aluminum Clad Steel
2.8M3
Bare ACSR Aluminum Conductor Steel Reinforced cable
Bare conductor
All Aluminum Alloy Conductor AAAC bare cable
Bare conductor
-
Bare All Aluminum Conductor AAC cable
Bare conductor
AAC/AAAC/ACSR cable bare conductor
overhead power cable