user login

6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard

0.2~158.0 USD
Min. Order: 500 Meter
Trade Term: FOB
Payment Terms: L/C, D/P, D/A, T/T, WU
Supply Ability: 50000 meters per week
Place of Origin: Henan

Company Profile

Location: Zhengzhou, Henan, China (Mainland)
Business Type: Manufacturer, Trading Company

Product Detail

Model No.: 6.35/11KV power cable
Means of Transport: Ocean, Air, Land
Application: Construction
Type: Medium Voltage
Insulation Material: XLPE
Jacket: PVC
Conductor Material: Copper
Brand Name: aobest
standard1: IEC60502
Standard 2: AS/NZS
Standard 3: GOST
screen: copper wire then copper tape
insulation color: black
sheath color: red or black
packing: steel drum
quality warranty: 20years
certificate: ISO9001
inspection: any inspection party accepted
Production Capacity: 50000 meters per week
Packing: steel reel
Delivery Date: 10days
Show

Product Description

6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard
Cable structure
  • Circular bare copper core, stranded according to HD 383, IEC 60228
  • Inner semi-conducting coating
  • Core insulation of cross-linked polyethylene (XLPE)
  • Insulation thickness: 6/10 kV = 3,4 mm; 12/20 kV = 5,5 mm; 18/30 kV = 8,0 mm
  • Outer semi-conducting coating spliced with the insulation
  • Tape of conductive material
  • Screening of copper wires and one or two copper tapes contrary applied
  • Wrapping with non-conducting tape
  • Sheath of PE compound, color black, sheath thickness 2,5 mm
Technical data
  • XLPE-insulated cable according to DIN VDE 0276 part 620, HD 620 and IEC 60502, GOST standard.
  • Temperature range max. +90 °C during installation from -5 °C to +70 °C Short circuit temperature 250 °C (up to 5 seconds)
  • Nominal voltages Uo/U 6/10 kV, 6.35/11KV, 12/20 kV, 18/30 kV, 19/33KV
  • Minimum bending radius approx. 15 x cable diameter
Application
Cable suitable for installation in cable ducts, power plants as well as for outer laying into earth, water or for installation in distribution boards. Due to its good shaping characteristics, this cable can also be laid even in difficult line guideways. To avoid the influence of the outer interferences, an adherent semiconductive layer is extruded between the conductor and the insulation. We recommend the use of stripping tool for correct installation.

Type: rm Type
Size:


Nominal
cross section
mm2
Insulation
Thickness
mm
Sheath thickness
mm
Overall dia.
mm
Weight
kg/km
253.41.622.30535
353.41.623.30592
503.41.724.40666
703.41.726.10773
953.41.827.50885
1203.41.829.001000
1503.41.930.551136
1853.41.932.331286
2403.42.034.901525
3003.42.137.401776
4003.42.240.102144

We focus on different cables production with full experiences, we provide best quality goods at lower price, for more information, please email us!
6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard
6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard
6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard
6.35/11KV XLPE insulated PE sheathed rm type cable GOST standard
Post Buying Request