RHZ1-OL Aluminum XLPE power cable
Application
Aobest RHZ1-OL is used for transportation of medium voltage power. Can be used for industrial installations or for a distribution network. Designed for fixed installations indoors, outdoors or in burried installations.
Construction
Conductor: Electrolytic compressed aluminium, class 2.
Semiconducting layer around the conductor
I
nsulation: XLPE.
Semiconducting layer around the isolation. Easy strippable
Screen
Screen of Cu threads and Cu tape
Outer sheath
Halogen free polyolefine, red
Construction comment
Hygroscopic tape wich completely covers the screen
Technical data
Working temperature
+90° C
Rated voltage
6/10 kV 12/20KV 18/30KV
Bending radius
15 x cable diameter
Approvals
IEC 60502-2, CE, RoHS
specification of 6/10KV RHZ1 power cable
size | Current Value A | Dia mm | Weight kg/km |
1x50mm2 | 170 | 24.6 | 675 |
1x70mm2 | 210 | 26.1 | 764 |
1x95mm2 | 255 | 27.6 | 860 |
1x120mm2 | 295 | 28.9 | 964 |
1x150mm2 | 335 | 30.3 | 1055 |
1x185mm2 | 385 | 32.9 | 1256 |
1x240mm2 | 455 | 35.3 | 1455 |
1x300mm2 | 520 | 37.6 | 1678 |
1x400mm2 | 610 | 40.7 | 1974 |
1x500mm2 | 720 | 44.3 | 2337 |
1x630mm2 | 840 | 49.3 | 2897 |
Many other PVC/XLPE power cable, rubber cable,control cable, bare conductor, ABC cable can be produced. More info needed, pls contact me freely.