- For 3-phase, four wire, WYE Applications
- Filters each of the three lines plus the neutral and ground line
- Both common mode and differential mode suppression from 50kHz to 30MHz
- Effective for both balanced and unbalanced loads
- Ground choke included
- Optional end bell kits available to shield input and output terminals
- AYP single stage for lower noise environments
- AYT dual stage provides highest performance
Ordering Information

Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
20AYP6C | 20AYT6C |
30AYP6C | 30AYT6C |
45AYP6C | 45AYT6C |
60AYP6C | 60AYT6C |
Specifications
Maximum leakage current, each Line to Ground: |
| @ 120 VAC 60 Hz | 1.4 mA |
| @ 250 VAC 50 Hz | 3.4 mA |
| | |
Hipot rating (one minute): |
| Line to Ground | 1500 VAC |
| Neutral to Ground | 1500 VAC |
| Line to Neutral | 1450 VDC |
| | |
Operating Frequency: | 50 / 60 Hz |
| | |
Rated voltage (max.): | |
| Phase to Phase | 440 VAC |
| Phase to Neutral / Ground | 250 VAC |
| | |
Rated Current: | 20A to 60A |
| |
Operating Ambient Temperature Range (at rated current Ir): |
| -10°C to +40°C |
In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir √(85-Ta)/45 |
Electrical Schematics
AYP6C Models

AYT6C Models

Case Styles

Case Dimensions
Part No. | A* | B | C | D | E |
(max.) | (max.) | (max.) | ± .030 | ± .015 |
± .76 | ± .38 |
20AYP6C 30AYP6C | 8.82 | 5.57 | 2.56 | 4.616 | 1.50 |
224.0 | 141.5 | 65.0 | 117.2 | 38.1 |
|
45AYP6C 60AYP6C | 9.43 | 6.92 | 4.82 | 5.950 | 3.75 |
239.5 | 175.8 | 122.4 | 151.1 | 95.3 |
|
20AYT6C 30AYT6C | 13.82 | 5.57 | 2.56 | 4.616 | 1.50 |
351.0 | 141.5 | 65.0 | 117.2 | 38.1 |
|
45AYT6C 60AYT6C | 13.83 | 6.92 | 4.82 | 5.950 | 3.75 |
351.3 | 175.8 | 122.4 | 151.1 | 95.3 |
|
* For end bell covering terminals and connections, add: |
20A & 30A | 5.57 | |
141.48 |
45A & 60A | 6.45 |
163.83 |
Accessories
Mounting bracket kit with captive nuts:
AA400: 20A & 30A versions
AA405: 45A & 60A versions
Protective cover for use with mounting bracket (Available in Europe only):
AA406A: 20A & 30A versions
AA407A: 45A & 60A versions
End bell kit (bracket and cover) with captive nuts:
AA406: 20A & 30A versions
AA407: 45A & 60A versions
Additional captive nuts
AA401: 10 nuts

Performance Data
Typical Insertion Loss |
Measured in closed 50 ohm system |
|
20AYP6C | 30AYP6C | 45AYP6C | 60AYP6C |
20AYT6C | 30AYT6C | 45AYT6C | 60AYT6C |
Minimum Insertion Loss in dB: |
Measured in closed 50 ohm system |
| | |
Common Mode / Asymmetrical (Line to Ground) | | Differential Mode / Symmetrical (Line to Line) |
| |
|
Current Rating | Frequency - MHz | .05 | .1 | .15 | .5 | 1 | 5 | 10 | 30 |
| AYP6C | 20A | 22 | 32 | 39 | 55 | 56 | 65 | 65 | 54 | 30A | 15 | 24 | 30 | 55 | 55 | 61 | 63 | 50 | 45A | 8 | 19 | 25 | 49 | 49 | 56 | 58 | 45 | 60A | 5 | 16 | 22 | 50 | 50 | 54 | 54 | 47 | AYT6C | 20A | 45 | 63 | 70 | 75 | 75 | 75 | 75 | 65 | 30A | 29 | 53 | 61 | 75 | 75 | 75 | 75 | 60 | 45A | 15 | 39 | 43 | 75 | 75 | 75 | 75 | 50 | 60A | 12 | 37 | 46 | 75 | 75 | 75 | 70 | 45 |
| | Current Rating | Frequency - MHz | .05 | .1 | .15 | .5 | 1 | 5 | 10 | 30 |
| AYP6C | 20A | 20 | 38 | 50 | 65 | 65 | 65 | 60 | 52 | 30A | 18 | 28 | 43 | 65 | 65 | 65 | 59 | 48 | 45A | 8 | 20 | 27 | 60 | 65 | 65 | 56 | 43 | 60A | 20 | 24 | 27 | 60 | 65 | 65 | 56 | 50 | AYT6C | 20A | 27 | 56 | 65 | 70 | 70 | 70 | 70 | 70 | 30A | 17 | 46 | 55 | 75 | 75 | 75 | 75 | 70 | 45A | 14 | 41 | 50 | 75 | 75 | 75 | 75 | 65 | 60A | 26 | 50 | 58 | 75 | 75 | 75 | 75 | 60 |
|