Min. Order: | 10 Piece/Pieces |
---|---|
Trade Term: | FOB |
Payment Terms: | PAYPAL, T/T, WU |
Supply Ability: | 2000/month |
Place of Origin: | Beijing |
Location: | Beijing, China (Mainland) |
---|---|
Business Type: | Manufacturer, Trading Company |
Main Products: | CO2 Monitors/ Controllers/ Transmitters, Digital Thermostats, Humidity Controllers, CO/ VOC/ O3 Gas Detectors |
Model No.: | F2000IAQ-CO2-31XX/51XX |
---|---|
Means of Transport: | Air |
Output: | Switching Transducer |
Theory: | Others |
Usage: | Gas Sensor |
Brand Name: | Tongdy |
Warranty: | free 2 years under the normal use |
aftersale service: | lifetime free tech support |
company type: | manufacturer |
sensing element: | Non-Depressive Infrared Detector (NDIR) |
shipment way: | DHL,EMS,UPS,TNT etc |
Production Capacity: | 2000/month |
Packing: | standard package |
Delivery Date: | depend on your quantities |
Gas detected | Carbon Dioxide (CO2) |
Sensing element | Non-Depressive Infrared Detector (NDIR) |
Temperature sensor | NTC |
Temperature correction | Self compensation |
CO2 NDIR life | 15 years |
Consumption | 3.5W/ Max, 2.5W/ Average |
Accuracy@25℃(77℉) | ±40ppm + 3% of reading |
Stability | <2% of FS over life of sensor (15 yr typical) |
Warm up time | 2 hours (first time) 2 minutes (operation) |
CO2 measuring range | 0~2000ppm, which is default value 0~(1,000~20,000)ppm, programmable selection |
CO2 setting & Display resolution | 1ppm |
Temperature measuring range | 0~50℃(32~122℉) |
Temperature setting range | 5~45℃(41~113℉) |
Option: 1X dry contact output | Rated currency for contact point: 3A 220VAC/30VDC, resistance load |
Option: RS485 communication interface | 9600/14400/19200(default)/28800/38400bps rates selectable by program,15KV protection for static, independent address setting |
Operation condition | 0~50℃ (32~122℉), 0~95%RH without condensing |
Power supply | 220VAC/110VAC or 24VAC 50/60HZ±10% |
Weight | 380g |
Dimensions | 130mm×90mm×40mm |
Connections Interface | Locate in interface of connection |
Installment standard | 65mm×65mm or 2"×4" wire box |
Wiring standard | Wire section area<1.5mm2 |
Approval Standard | CE-Approval |
Programming and selection | DIP switches inside and external push-buttons |