Item Description |
Input | Rated Voltage and Frequency | 400V/50Hz/60Hz,Voltage:±15%;Frequency:±5% |
200V/50Hz/60Hz,Voltage:±15%;Frequency:±5% |
Rated Voltage | Three Phase:400V(proportional to input voltage) |
Three Phase:200V(proportional to input voltage) |
Output | Rated voltage | Three-phase 0~input voltage VAC |
Control Function | Control Method | SVPWM |
Control Mode | V/F Control/Current Vector Control |
Torque Feature | With torque compensation and slip compensation, start torque can reach 150% at 1.0Hz |
Frequency Control Range | 0.1~400Hz |
Frequency Accuracy (Temperature Changing) | Digital Instruction:±0.01%(-10℃~+40℃) |
Analog Instruction: Max. Frequency x 0.2%Hz (25℃±10%) |
Setting Resolution | Digital Instruction:0.01Hz; Analog Instruction: Max. frequency x 0.1%Hz |
Output Resolution | 0.01Hz |
Overload capacity | General Mode (G):150% rated output current for 1 minute |
Blower/Pump Mode (P):120% rated output current for 1 minute |
Frequency Setting Signal | 0~10V(20kΩ),0~20mA(250Ω),4~20mA(250Ω) |
Acceleration/Deceleration Time | 0.0~3600 seconds (acceleration/deceleration time shall be set respectively) |
Performance | Braking Torque | About 20% without braking resistor, and about 125% with braking resistor |
V/F Mode Classes | 12 preset V/F mode and programmable V/F mode |
Instantaneous Over Current | General Mode(G):About 250% AC motor driver rated current |
Blower/Pump Mode(P):About 200% AC motor driver rated current |
Over Load | General Mode(G):150% rated output current for 1 minute before sliding stop |
Blower/Pump Mode(P):120% rated output current for 1 minute before sliding stop |
Over Voltage | Motor stops sliding when rectifier output voltage exceeds 410V(200V class)/820V(400V class) |
Under Voltage | Motor stops sliding when rectifier output voltage drops down to 190V(200V class)/380V(400V) or lower |
Instantaneous Power-Failure Compensation | Instant stop when instantaneous power-failure lasts for 15ms or longer.(Default setting) According to standard setting, if the power –failure is shorter than 2 seconds, continue operation. |
Heat Sink Overheat | Thermistor protection, takes effect when temperature exceeds 105Ω |
Speed Loss Protection | Speed loss protection during acceleration, deceleration and constant speed operation |
Grounding Failure | Electronic circuit protection, takes when leakage current reaches 50% of AC motor driver rated current. |
Environment | Environment Temperature/Humidity | -10℃~+40℃, 90%RH and lower (no dewing) |
Operation Location | Altitude below 1000M,indoor use(no corrosive gas, liquid, no dust) |
Storage Temperature | -20℃~60℃ |
Vibration | Below 20Hz 9.8m/s2(1G) , 20~50Hz 5.88m/s2(0.6G) |