Min. Order: | 1 Piece/Pieces |
---|---|
Trade Term: | FOB |
Payment Terms: | L/C, D/P, D/A, T/T, WU |
Supply Ability: | 20000/year |
Place of Origin: | Hubei |
Location: | China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | ZN63A(VS1)-12 |
---|---|
Means of Transport: | Ocean, Air, Land |
Certification: | ISO9001 |
Production Capacity: | 20000/year |
Packing: | cartons |
Delivery Date: | as you request |
Main Technical Data | ||||
Rated voltage | kv | 12 | ||
Rated lighting impulse withstand voltage | kv | Interphase or to ground 75,fructure 80 | ||
Rated short-time power frequency withstand voltage(dry) | kv | Interphase or to ground 42,fructure 48 | ||
Rated short-circuit breaking current | kA | 20/25 | 31.5 | 40 |
Rated current | A | 630/1250 | 630/1250/ 1600/2000/ 2500/3150 | 1250/1600/ 2000/2500/ 3150/4000 |
Rated thermostability current(valid) | kA | 20/25 | 31.5 | 40 |
Rated dynamic stability current(peak) | kA | 50/63 | 80 | 100 |
Rated short-circuit making current(peak) | kA | 50/63 | 80 | 100 |
Power frequency withstand voltage of secondary circuit(1 min) | v | 2000 | ||
Rated working current of overcurrent and tripping coil | A | 5 | ||
Rated operating sequence | 0-0.3s-CO-180s -CO/0-180s-CO-180s-CO(40KA) | |||
Rated thermostability time | s | 4 | ||
Rated single/back to back capacitor bank breaking current | A | 630/400 800/400(40kA) | ||
Mechanical life | times | 10000 | ||
Note:It need to be forced coolingwhen rated current is 4000A Rated characteristics can be given on requirment |