Rated voltage | 24KV |
Rated current | 1250/1600A |
Rated frequency | 50HZ |
Rated short-time power frequency withstand voltage (1min) | 79KV |
Rated lightring impulse withstand voltage (1 min) | 145KV |
Rate short-circuit breaking current | 31.5KA |
Rate short-circuit making current(peak) | 80KA |
Rated operations of short-circuit breaking current interruption | 20 times |
Rated single capacitor bank breaking current | 400A |
Rated short-time withstand current | 31.5KA |
Rated peak withstand current | 80KA |
Rated duration of short-circuit | 4s |
Mechanical life | 10000 times |
Contact closing force due to bellows and atmosphere | 120±50N |
Conterforce at rated contact stroke | 190±60N |
Circuit resistance at rated contact atmosphere force | ≤20μΩ |
contact erosion limit | 3mm |
Shelf life | 20 years |
Weight of moving parts | ≤1.6kg |
| |