High voltage ZW38-40.5 overhead ceramic insulator outdoor AC high voltage vacuum circuit breaker

Min. Order: 1 Set/Sets
Payment Terms: L/C, D/P, D/A, T/T, WU
Place of Origin: Hubei

Company Profile

Location: Wuhan, Hubei, China (Mainland)
Business Type: Manufacturer, Distributor/Wholesaler

Product Detail

Means of Transport: Ocean, Air, Land
Type: Vacuum
Poles Number: 3
Brand Name: feite
Packing: as required
Delivery Date: within two weeks
Show

Product Description

 ZW38-40.5 series overhead ceramic insulator high voltage outdoor circuit breaker is a type of 50HZ three-phase alternating current high voltage switch equipment. It 's mainly used in normal operation and short-circuit protection for all kinds of power grid. Attached type CT19-IVB spring operating structure and electromagnet operating structure can manipulate electric opening and closing in a distance, or accumulate energy for manual operation.
Vacuum interrupter is put in the insulator fulfilled with SF6 to protect it from effect of outer circumstances, thus anti-contamination, anti-condensation, and reliable. Each VCB can equip with 6-12pieces of current transformer according to customer's requirement.
The design performance strictly sticks to our national standard GB1984 - 89 for high voltage alternating current vacuum circuit breaker, and meet the requirements of International Electro technical Commission (IEC) IEC-56 for high voltage alternating current vacuum circuit breaker. It has characteristics of simple structure, small size and easy mounting,.
Ambient temperature:
max +40°C min -15°C(conveyance under -30°C is allowed)
2 Altitude: ≤1000m
3 Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity≤90%; daily average saturated vapor pressure ≤2.2*10-3 MPa; monthly average value  ≤1.8*10-3 MPa
4 Earthquake intensity: ≤8 degree
5 The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution
Order instruction
Complete model and order quantity of the product
Rated current, rated voltage, distance of each poles
Rated short circuit breaking current, operation voltage
Required accessory and quantity
Other requirement please contact with us directly
Main Technical Data
Rated voltage                                                           kv40.5
Rated current                                                             A2000
Rated short-circuit breaking current                              kA31.5
Rated short-circuit making current                              kA80
Rated operations of short-circuit breaking current interruptiontimes20
Rated out of phase breaking currentkA8
Out of phase grounding faulting breaking currentkA27.4
Rated operating sequence                                             0-0.3-CO-180s -CO
Rated duration of short-circuit                              s4
Rated short-time withstand current                         kA31.5
Rated peak withstand current                               kA80
Opening timems3-65
Closing timems40-100
Average closing speed                                    m/s1.0±0.35
Average opening speed                                   m/s2.0±0.35
Contact bouncing duration at closing operation                ms≤8
Three-pole simultaneity                                     ms≤3
Rated voltage fufilled with SF6Mpa(CT attached) 0.02(CT attached) 0.2
Weightkg(without CT) 750
1000/1150/1300(6pieces CT/
9pieces CT/12pieces CT)
Note:Rated characteristics can be given on requirment
Post Buying Request