Min. Order: | 1 Piece/Pieces |
---|---|
Trade Term: | FOB |
Payment Terms: | L/C, T/T |
Supply Ability: | 100pcs/day |
Place of Origin: | Guangdong |
Location: | Shenzhen, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Main Products: | Online DSP UPS, Uninterrupted Power Supply UPS, Inverters, America UPS, LINE- INVERACTIVE UPS |
Model No.: | PV10-400KVA |
---|---|
Means of Transport: | Ocean, Air, Land |
Application: | Telecommunications |
Phase: | Three Phase |
Type: | On-line |
Protection: | Short Circuit |
Brand Name: | HRD/OEM |
Weight: | 100KG+ |
Output Voltage: | 380/400/415VAC |
color: | black/white |
output PF: | 0.8 |
LCD display: | 7 inch larger LCD |
Event log: | 1000pcs |
technology: | based on Reillo UPS |
ECO Function: | standard |
EPO Function: | standard |
parallel: | using common battery bank |
battery type: | 3 types |
system: | DSP control |
Production Capacity: | 100pcs/day |
Packing: | wooden packing as export standards |
Delivery Date: | 4 weeks after payment |
12 Pulse Power Supply 10-600KVA Online Low Frequency UPS 3phase
Technical specification
1) 10-120KVA specification
Model | PV3310ii | PV3315ii | PV3320ii | PV3330ii | PV3340ii | PV3360ii | PV3380ii | PV33100ii | PV33120ii | ||||||||
Capacity | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | ||||||||
system | |||||||||||||||||
Output PF | 0.8(lag) | ||||||||||||||||
System efficiency (inverter mode) | 92%(@100% load) ;90% @50%load; | ||||||||||||||||
System efficiency (ECO mode) | 98%(@100%load) | ||||||||||||||||
Maximum leakage current | 100(mA) | ||||||||||||||||
MTBF | Above 200,000hours | ||||||||||||||||
Dry contact | Standard: 3 types signal(BAT. low,battery mode,bypass /failure); Optional:14 dry contact ; output: 12Vdc 80mA | ||||||||||||||||
Communication interface | Standard RS232,optional: RS485 / MODBUS | ||||||||||||||||
Operation temperature | 0 ~ 40 °C | ||||||||||||||||
Humidity | 95 % (non-condense) | ||||||||||||||||
Cooling | Forced air(speed varying according to load percent) | ||||||||||||||||
Max. altitude | Within 1000m(every 100increase,capacity decrease -1%),Maximum 4000m | ||||||||||||||||
Noise (dB) | 52 ~ 58 | ||||||||||||||||
IP protection (EN 60529) | IP20 | ||||||||||||||||
Input/output way | Bottom /rear | ||||||||||||||||
Safety standard | safety:GB4943 ,EN 50091-1;EMI:GB7260.2,GB/T 17626.2~5EMC, EN 50091-2 | ||||||||||||||||
Physical | |||||||||||||||||
W *D*H(mm) | 600*600*1280 | 800*800*1480 | 800*800*1800 | ||||||||||||||
Weight(Kg) | 195 | 210 | 220 | 305 | 340 | 500 | 600 | 800 | 950 | ||||||||
AC input | |||||||||||||||||
Rated voltage | 380/400/415VAC Three-phase three-wire | ||||||||||||||||
Input voltage range | ± 15 %- ± 25 % adjustable) | ||||||||||||||||
Rate frequency | 50 / 60 Hz auto-sense | ||||||||||||||||
Frequency range | 50/60Hz+/-5Hz | ||||||||||||||||
Input soft start function | 0 - 100%,10-300s(settable) | ||||||||||||||||
Input power factor | Reachable 0.99(plus harmonic filter) | ||||||||||||||||
Input current harmonic component(THDi ) | Can<5%(plus harmonic filter) | ||||||||||||||||
Max. input current [A] | 18 | 27 | 36 | 54 | 72 | 108 | 144 | 180 | 216 | ||||||||
The output characteristic of the rectifier | |||||||||||||||||
Maintain the voltage (20°C) | Battery type1 and 2 :V =435Vdc (2.266 x el.) | ||||||||||||||||
Battery type 3 :V =424Vdc (2.21 x el.) | |||||||||||||||||
Battery type 0:the voltage value between type 1and 2, Voltage regulating range: V =400~460Vdc | |||||||||||||||||
Charging voltage (20°C) | Battery type1 and 2 :V (%recharging<95%) = 445Vdc (2.32 x el.) | ||||||||||||||||
Battery type 3 :V (%recharging<95%) = 460Vdc (2.4 x el.) | |||||||||||||||||
Battery type 0: the voltage value between type 1and 2, Voltage regulating range: V =400~460Vdc | |||||||||||||||||
The highest charging voltage | 445V | ||||||||||||||||
The charger output voltage regulation accuracy | 1% | ||||||||||||||||
DC ripple voltage component | ≤1% | ||||||||||||||||
Battery | |||||||||||||||||
Unit number(rated voltage) | 384VDC(360-384v,selectable) | ||||||||||||||||
Charging current settings | 0.1C(battery capacity) | ||||||||||||||||
The battery discharge end voltage | Battery type 1,2 and 3:no-load discharge current,V min=346 [V dc] | ||||||||||||||||
Battery type 1,2 and 3:output current =Ah capacity,V min=316 [V dc] | |||||||||||||||||
Battery type 1,2 and 3:output current >Ah capacity,V min=306 [V dc] | |||||||||||||||||
Battery type 0: the factory set the default values,V min=320 [V dc] Regulating range: V min =300~360[V dc] | |||||||||||||||||
Inverter output | |||||||||||||||||
Rated capacity [KVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 120 | ||||||||
Rated power [KW] | 8 | 12 | 16 | 24 | 32 | 48 | 64 | 80 | 96 | ||||||||
Rated voltage [V] | 380/400/415VAC three-phase four-wire | ||||||||||||||||
Rated current [A] | 12 | 18 | 24 | 36 | 48 | 72 | 96 | 120 | 144 | ||||||||
Phase voltage setting | 200 ~ 244 V (control board) | ||||||||||||||||
Peak factor | 3:1 | ||||||||||||||||
Waveform | Sine wave | ||||||||||||||||
Voltage phase shift (degrees) 100% balanced load | ± 1' | ||||||||||||||||
Voltage phase shift (degrees) 100% unbalanced load | ± 2' | ||||||||||||||||
Phase voltage difference 100% balance load | ± 1 % | ||||||||||||||||
Phase voltage difference 100% unbalanced load | ± 3 % | ||||||||||||||||
Total harmonic content(THD v) 100% linear load | <2% | ||||||||||||||||
Total harmonic content(THD v) 100% non-linear load | <5% | ||||||||||||||||
Steady-state voltage stability | ± 1 % | ||||||||||||||||
Transient voltage response | ± 5 % within 10ms | ||||||||||||||||
Rated frequency | Same as input | ||||||||||||||||
Frequency stability | When asynchronous,± 0.5 %;synchronization,± 2 % (can be set to ± 1~5 %,by the panel operation) | ||||||||||||||||
Overload | 600' / 10' / 1' (110/125/150% rated current) | ||||||||||||||||
Short circuit 0.1s | Double input | ||||||||||||||||
Inverter efficiency (load 100%) | 98% | ||||||||||||||||
Bypass | |||||||||||||||||
Rated capacity [KVA] | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 120 | ||||||||
Rated voltage [V] | 380/400/415VAC Three-phase four-wire | ||||||||||||||||
Input voltage range | ±15 %(can be adjusted from the control panel ± 10 %,± 20%) | ||||||||||||||||
Rated frequency [Hz] | 50 / 60 | ||||||||||||||||
Frequency range | ±2 %(can be adjusted from the control panel ± 5 %) | ||||||||||||||||
"STAND-BY ON"(Eco mode, the bypass switch to inverter)transfer time | 2~5ms | ||||||||||||||||
Inverter/bypass transfer time | <1ms | ||||||||||||||||
Overload | 10'/1'/18" (150/175/200% Rated current) | ||||||||||||||||
Standard configuration | Feed flow protection, bypass independently isolated |
NOTE: 120VAC power grid 10-200kva are available;