user login

150KW Diesel Generator Set Cummins engine

10000.0~100000.0 USD
Min. Order: 1 Set/Sets
Trade Term: FOB
Payment Terms: T/T, WU
Supply Ability: 500sets/month
Place of Origin: Hebei

Company Profile

Location: China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: CDC [S/L]-150
Means of Transport: Land
Output Type: AC Three Phase
Brand Name: Dafeng
Speed: 1500rpm/1800rpm
Frequency: 50hz/60hz
Rated Power: 150KW/160KVA
Rated Voltage: 230V
Rated Current: 270A
Usage: mining,railways,factories,business,hospitals
Production Capacity: 500sets/month
Packing: plastic wrapping
Delivery Date: 2-3 weeks
Show

Product Description

Engine data
Manufacturer / Model
DCEC Cummins 6CTA8.3-G2,4-cycle
Air Intake System
Turbo, Water/Air Cooling
Fuel System
PB/W type fuel pump
Cylinder Arrangement
6 in line
Displacement
8.3L
Bore and Stroke
114×135(mm)
Compression Ratio
17/1
Rated RPM
1500rpm
Max. Standby Power at Rated RPM
180KW/244HP
Governor Type
Electronic

Alternator Data
Manufacturer
Stamford/ Leroy Somer etc
Number of Phase
3
Connecting Type
3 Phase and 4 Wires, "Y" type connecting
Number of Bearing
1
Power Factor
0.8
Protection Grade
IP23
Altitude
≤1000m
Exciter Type
Brushless, self-exciting
Insulation Class, Temperature Rise
H/H
Telephone Influence Factor (TIF)
<50
THF
<2%
Voltage Regulation, Steady State
≤±1%
Alternator Capacity
160KVA
Alternator Efficiencies
92.3%
Air Cooling Flow
0.514m3/s

Generating set data
Voltage Regulation
≥±5%
Voltage Regulation, Stead State
≤±1%
Sudden Voltage Warp (100% Sudden Reduce)
≤+25%
Sudden Voltage Warp (Sudden Increase)
≤-20%
Voltage Stable Time (100% Sudden Reduce)
≤6S
Voltage Stable Time (Sudden Increase)
≤6S
Frequency Regulation, Stead State
≤5%(adjustable)
Frequency Waving
≤0.5%
Sudden Frequency Warp (100% Sudden Reduce)
≤+12%
Sudden Frequency Warp (Sudden Increase)
≤-10%
Frequency Recovery Time (100% Sudden Reduce)
≤5S
Frequency Recovery Time (Sudden Increase)
≤5S
operation
After diesel generator installed, you can put into power, before each start, at least the following items should be checked
1.whether unit surface and around has debris
2.keep the into and exhaust channel of the engine room is smooth
3.the cooling liquid tank is normal
4.the air filter indicator directs normal
5.lubricating oil level is within normal range
6.the fuel valve is open, the supply of fuel to engine is normal
7.battery cables are connected correctly
8.power load device is ready,when the generator directly with the load, breaking the air switch before start.
Post Buying Request