user login

Network quality meter

Min. Order: 1 Piece/Pieces
Trade Term: FOB
Payment Terms: L/C, T/T
Supply Ability: 100000
Place of Origin: Shanghai

Company Profile

Location: China (Mainland)
Business Type: Manufacturer, Distributor/Wholesaler

Product Detail

Model No.: ACR330ELH
Brand Name: Acrel
EN 61326:2006: EN 61010-1:2001
Production Capacity: 100000
Packing: paked by case
Delivery Date: within 2 weeks
Show

Product Description

1. General
        ACR330ELH/M is one of multifunction analyzers, and it can measure all the data of electrical network. At the same time, they can measure more than 31th harmonics and display the  harmonics by bar graphic and by wareform. According to crest factor, K factor, THFF etc., the user can analyze the power quality of electrical network.
         It complies EN 61326:2006 and EN 61010-1:2001 and RoHS Directive 2002/95/EC.
           
- Communication and programming via optical interface, or remotely via RS485 output
- Energy: measurement import kWh, kvarh, kva and export kWh and kvarh in class 0.5
- Display of harmonics by order to 31st
- Display of harmonics by bar graphic and by wareform
- Up to 4DI & 2DO configurable, one DO can be used as Alarm.
- 16 SOEs
- Possibility of upgrading the embedded software via the optical interface
- Graphic display: Fresnel diagram, harmonics in bar graph form, U, I displayed as gauges
             
2. Technical Feature
- Measurement: VL1, VL2, VL3,VL12, VL23, VL31,AL1, AL2, AL3, ∑AL, F,
                       ∑P, P1,P2,P3, ∑Q, Q1,Q2,Q3,∑S, S1,S2,S3,∑PF, PF1,PF2,PF3,
                       MD kW, MD kvar, MD kva, +kWh, +kvarh, kvah, -kWh, -kvarh,
                       31 harmonics,
                       CF,THFF,KF,UF,UPEAK,UVECTOR,IVECTOR
- Network: 1P2W, 3P3W, 3P4W
- Frequency 45 ~ 65Hz
- Normal: AC 100V, 400V; Overloading: 600V(continuous), 1000V / 30s; Consumption: < 0.2VA
- Current: AC 1A, 5A; Overloading: 6A(continuous), 50A /10s; Consumption: < 0.2VA
- Accuracy Frequency 0.01Hz, reactive energy 1 class, others 0.5 class
- Display: LCD
- Power supply: AC/DC 85~270V; consumption: < 4VA
- Isolation: Power / current input / voltage input: AC2kV/1min;Power / logic inputs / RS485: AC1.5kV/1min;
Inputs / outputs / housing > 5MΩ
- Working T: -20C ~ +55C; Storing T: -30C ~ +70C
- Relative humidity: 5% ~ 95% Non-Condensing;
- Altitude: < 2500m
- Harmonics Individual to 31st order
- Norms:
IEC61000-4-2: 1995 Electrostatic discharge immunity test Level 3
IEC61000-4-3: 1995 Radiated, radio-frequency, Level 3
IEC61000-4-4: 1995 Electrical fast transient pulse immunity test Level
IEC61000-4-5: 1995 Surge immunity test Level 3
                  
3. Options:
- /P: Pulse output Opt coupler pulse output
- /C: Communication RS485 (Modbus-RTU)
- /K: Logic input (DI) 4 drying contact inputs, with +5V power; Logic output (DO) 2 NO contacts (AC 250V/3A,
DC 30V/3A)
Post Buying Request