Product Description
BATTERY MONITORING SYSTEM
Intelligent Battery Monitor
Continuous 24/7 on-line monitoring
One CELLCHECK monitor one cell, including internal resistance, voltage and temperature
Software is available to collect data from CELLCHECK
RS485 port with Optical isolation, meet MODBUS protocol, easy to access UPS controller
Easy to install without specialized training
Overview
CELLCHECK intelligent battery monitor is Huasu introduced specifically for single cell design of products. CELLCHECK combines the advanced technology with patented for the most thorough stationary battery health analysis in the industry.
Features
Full resistance, battery temperature and voltage monitoring for comprehensive battery state of health analysis
String voltage, string current and ambient temperature monitoring(need VCT unit)
Automatic analysis of battery condition to estimate remaining battery capacity, indicating that the battery needs replacement or maintenance
(need CM unit)
With a certain amount of storage space for history data
Panel light flashes and can be read from the RS485 port when warning
All operating parameters can be set by RS485 port
Use software to manage multiple strings, check real-time alerts and historical data
Specifications
Environmental
Operating temperature:-5℃~50℃,5%~90%RH
Storage temperature: -10℃~70℃,5%~90%RH
USE FOR
2V,6V or 12V battery, capacity from 30AH to 1000AH
Power Requirements
CELLCHECK:powered from the battery,less than 60mA(2V) or 30mA(12V)
VCT unit:DC10~35V
CM unit:DC10~35V
Protection
Test load and power paths are fused, reverse polarity and overvoltage protection for power input
Measurement Range & Accuracy
String voltage:20~600V,0.5%+0.2V
Cell voltage:1.5~2.5V,0.1%+1mV
7~16V,0.1%+10mV
Internal resistance:100~65535uΩ
2%+3 uΩ(2V battery, repeatability)
2%+30uΩ(6V,12V battery, repeatability)
Temperature:-10℃~+70℃, 0.5℃
String current:0~100A(optional), 2%+0.5A
Communications Interfaces
CELLCHECK:RS485, meet MODBUS protocol, support 200 devices on each bus
CM unit:RS485, Ethernet 10/100 Mbps, meet
MODBUS protocol
Insulation
2000VAC
Installation
Paste on battery or rail mounting
Weight
CELLCHECK: 135g
Options
1. VCT unit
Use to monitor string voltage, current and temperature.
2. CM unit
Use to manage up to 10 strings and 200 cells each string.
3. Current sensor
Use to monitor string current with VCT unit.
4. LCD unit
Use to read data from CM unit and display.
5. Software
Software can be installed on PC and read and display data from CM unit.
Applications
UPS
Telecommunications
Battery supplied applications
Utilities
Fire &Safety system
Remote monitoring