user login

200KVA 11kv three phase transformer temperature switch

Min. Order: 1 Set/Sets
Payment Terms: L/C, T/T
Supply Ability: 200sets/month
Place of Origin: Zhejiang

Company Profile

Location: Jinhua, Zhejiang, China (Mainland)
Business Type: Manufacturer, Trading Company

Product Detail

Model No.: ss9
Means of Transport: Ocean
Phase: Three
Coil Structure: Toroidal
Coil Number: Autotransformer
Usage: Power
Brand Name: Sasun
rated voltage: 6.3KV,10KV,11KV,13.2KV,13.8KV,15KV,20KV,22KV
rated capacity: 5,10,20,30,50,63,80,100,125,200,250,315,400,500...KVA
Production Capacity: 200sets/month
Packing: wooden cases
Delivery Date: 30days
Show

Product Description

1. Technical Data
11kv S9 Series three Phase Oil Immersed Distribution Transformer
Instruction
         The transformer is a transformer whose interior is isolated from the air surrounding, so the transformer oil can not absorb the outer moisture and the oxygen since the change of transformer's volume could be fixed with the flexibility of corrugated tank structure. Then the aging speed of insulated material will be decreased. Before running the machine, the work of core suspension checkup is not necessary. Clients could also be free from the later maintenance and reparation. The reliability of products is visibly upgraded. Products is designed with PCCAD, the characters are conformed to IEC 60076 and GB 1094, and passed qualification ISO 9001.
       The coil is with high-intensity enameled wires (or paper wrapped wired). Bucket form or cake form, evenly coiled and installed. Its insulation structure is reasonable, and it has strong anti-shortcut capacity. All the screws will not become loose after long journey. All sealed parts use rubber, which could effectively anti-aging by heat, light and electricity, also emote controlled thermometer and pressure release valves which increase the reliability.
Characteristics
1. No devices like oil tank, and humidity absorber could assure the oil to be insulated from air and the oil could be used for 20 years consecutively without any treatment later
2. High qualified rubber used for the sealing
3. Oil filling in vacuum condition
Loss(kW) Weight (kg)(mm)Gauge
Rated CapacityVoltage Group(kV)Connection Method          (75)No-load currentImpedance Voltage (L)(W)(H)
(kVA)HVLVNo-loadLoad%%MachineOilGrossOutline DimensionVerticalHorizontal
50 Dyn11 Yyn00.171.1525.52001454659206101000450380
100 DYn50.231.921.83301656359206801100550450
125 0.272.261.73951857459607801120550470
160 0.292.691.650520588511607101180550520
200 0.343.161.558022599511907301190550520
250 0.413.761.4685245113012808201210650550
31523 0.494.531.4745260128513809101240650550
400220.4 0.585.471.3865305150014309501320650550
50020 0.696.581.29853351710152010201360750600
63015 0.837.871.111653852010168011501380850660
80011 0.989.41113354152315181012801430850660
100010 1.1511.5116555152985184012901540850660
12506 1.413.90.918906303460185013001730850660
1600 1.716.70.822207104015192013501790850700
2000 2.1820.40.825307304425202017702040820820
2500 2.5621.90.83165795526020801800213010701070
(Note): (Tapping range of high voltage) ±5%; ±2×2.5%, Frequency: 50Hz,60HZ.