1. Product Brief Introduction
The DTSD6006Type electronic three-phase multi-function watt-hour meter is a new type of multi-function meter; it accords with the correlative standard, rules of the nation. It has the function as high-accuracy, well stability, advanced technology and easy operation. The performance index of the meter accord with the technical requirements of nation standard, such as
GB/T17215-2002"Class 1 and 2 Static A.C Activewatt-hour Meter", GB/T17883-1999
"Class 0.2S and 0.5S Static A.C Activewatt-hour Meter",GB/T17882-1999"Class 2 and 3Static A.C ReactiveWatt-hour Meter", andDL/T645-1997"Multi-function watt-hour meter", the communication agreement accord withDL/T6451997.
2. Function and Features
-Forward direction, reverse direction and 4 quadrants are reactive power and demand, the time of max demand.
-Spit phone measuring;
-4 rates, 4 time zones,6 time period, 10 day time, 12 public holidays;
-Measuring power, demand, and power factor at current time;
-The data can be congealing auto and recording data within 12 months;
-The active forward&reverse direction and the reactive 4 quadrants output via pulse. The pulse width can be setup by controller or Rs485;
-The infrared controller will display the item;
-The lineate communication and the infrared wireless communication are accord to DL/T645-1997;
-Li can be mounted the meter key stoke-display or circle -display when power is off. Al l the data can be setup by controller of software;
-Recording affairs parameters function
- -Meter reading function at power off;
-Recording the load;
-It is easier of electric department centralized management;
-Alarming over load function;
- Transformer magnification can be setup;
-All the data and information can be display via LCD;
-Measuring the voltage, current\power of the each meter all the time;
-It has the recording feature of loss voltage, loss current, coincidence rate of the voltage, power off, programmer; adjust the time and so on;
-It has the function of program forbid and demand replacement;
-Power break awakening function;
-Two sets of Battery, one (3.6V)is used for keeping data, and another (6V) is used for coping. They are easier to change.
3. Main Technical Data
Rated Current (A) | 3×1.5(6),3×10(40),3×15(60),3×20(80),3×30(100) |
Rated Voltage (V) | Three-phase Three-wire 3×100V or 3×380V Three-phase Four-wire 3×220/380V or 3×57.7/100V |
Rated Frequency (Hz) | 50 or 60 |
Accuracy Class | Active: 0.5\Reactive:1.0 or Active:1.0\Reactive:2.0 |
Clock Error | ≤0.5sec/per day (reference temperature); ≤1.0sec/per day (the backup lithium battery working time). |
Battery | Important lithium battery voltage:3.0 or 3.6V; Capacitance≥ 1000mAh; ;1200bps-19200bps;it has the program both in insider and outside; Update the data per 0.01degree;two sets of battery keep the clock and relative data; Setup the alarm data of the battery ;Loss and press blanking timing and electric consumption rate switches over time in the minimum interval For one minute. |