Min. Order: | 3 Piece/Pieces |
---|---|
Payment Terms: | L/C, T/T, WU |
Supply Ability: | 10000 pieces per month |
Place of Origin: | Zhejiang |
Location: | Ningbo, Zhejiang, China (Mainland) |
---|---|
Business Type: | Manufacturer, Distributor/Wholesaler |
Model No.: | PLCC-15/200 |
---|---|
Means of Transport: | Ocean, Air, Land |
Application: | Industrial |
Type: | Medium Voltage |
Insulation Material: | Rubber |
Jacket: | Rubber |
Conductor Material: | Others |
Brand Name: | PURANA |
Rated Voltage: | 15kV |
Rated Current: | 200A |
Material: | Silicon Rubber |
Applicable cable: | Copper core and XLPE cable with cross-sectional area 25mm2 to 400mm2 |
Application: | For connecting of 15kV transformer, switchgear and outdoor cable branch boxes |
Production Capacity: | 10000 pieces per month |
Packing: | In cartons |
Delivery Date: | 10 warking days after receiving downpayment |
1.Application:
1. Using the pushing tecnique to install the accessories in order to improve the sealing effect;
2. Applicable for 15kV 25-120mm2 single core and triple cores XLPE cable with cable core Cu or Al;
3. For extrusion type cable and other screened flexible cable;
4. For connecting of 15kV transformer, switchgear and outdoor cable distribution boxes.
2.15kV/200A loadbreak cable connector technical parameters:
Serial No. | Test Item | Unit | Parameter |
1 | Rated Voltage | kV | 15 |
2 | Rated Current | A | 200 |
3 | Power Frequency Withstand Voltage | kV/5min | 39 |
4 | Partial Discharge | kV≤10pC | 15 |
5 | Load Cycling Test | kV 500h | 23 |
6 | Lighting Impulse Withstand Voltage | kV | 95 |
7 | Negative Polarity DC Voltage | kV/15min | 35 |
3.15kV/200A cable terminal connector specification:
Serial No. | Cross-sectional Area / mm2 | Insulation Diameter | |
Min. | Max. | ||
1 | 25 | 16.00 | 17.80 |
2 | 35 | 16.50 | 19.00 |
3 | 50 | 18.00 | 20.00 |
4 | 70 | 19.50 | 21.50 |
5 | 95 | 21.5 | 23.5 |
6 | 120 | 23.00 | 24.50 |
4.Accessories:
A.Connecting plug
Serial No. | Test Item | Unit | Parameter | |
1 | Rated Voltage | kV | 15 | |
2 | Rated Current | A | 200/600 | |
3 | Power Frequency Withstand Voltage (5min) | kV | 39 | |
4 | Partial Discharge | kV/10pC | ≤15 | |
5 | Lighting Impulse Withstand Voltage | kV | 95 | |
6 | 15min DC Withstand Voltage | kV | 35 |
B.15kV/200A Two-ways Epoxy Resin Bushing
Serial No. | Test Item | Unit | Parameter | |
1 | Rated Voltage | kV | 15 | |
2 | Rated Current | A | 200 | |
3 | Power Frequency Withstand Voltage (5min) | kV | 39 | |
4 | Partial Discharge | pC | ≤10/15kV | |
5 | Lighting Impulse Withstand Voltage | kV | 95 | |
6 | 15min DC Withstand Voltage | kV | 35 |
C. 15kV/200A Insulating Protective Cap
Serial No. | Test Item | Unit | Parameter | |
1 | Rated Voltage | kV | 15 | |
2 | Rated Current | A | 200 | |
3 | Power Frequency Withstand Voltage (5min) | kV | 39 | |
4 | Partial Discharge | pC | ≤10/15kV | |
5 | Lighting Impulse Withstand Voltage | kV | 95 | |
6 | 15min DC Withstand Voltage | kV | 35 |
D.15kV/200A Earthing Connector
Serial No. | Test Item | Unit | Parameter | |
1 | Rated Voltage | kV | 15 | |
2 | Rated Frequency | Hz | 50 | |
3 | Power Frequency Withstand Voltage (5min) | kV | 39 | |
4 | Partial Discharge | pC/15kV | ≤10 | |
5 | Lighting Impulse Withstand Voltage | kV | 95 |
5. Installation example: