Min. Order: | 10 Piece/Pieces |
---|---|
Payment Terms: | TT |
Supply Ability: | 1000/Week |
Place of Origin: | Guangdong |
Location: | Dongguan, Guangdong, China (Mainland) |
---|---|
Business Type: | Manufacturer |
Model No.: | EA9910 |
---|---|
Means of Transport: | FOB |
Application: | Security / Monitoring / Alarm |
Phase: | Single Phase |
Type: | On-line |
Protection: | Overcurrent |
Brand Name: | EAST |
Weight: | 30 |
Output Voltage: | 220V |
Certificate: | ce |
Production Capacity: | 1000/Week |
Packing: | color |
Delivery Date: | 20days |
Capacity | 30KVA | 40KVA | 50KVA | 60KVA | 80KVA | 90KVA | 100KVA | 120KVA | |||
Rating | 24KW | 32KW | 40KW | 48KW | 64KW | 72KW | 80KW | 96KW | |||
Main input | voltage | 380V/400V ( Linear voltage ) | |||||||||
Phase | Three phase four wire | ||||||||||
P. F. | >0.99 | ||||||||||
Harmonic current (THDI ) | <3% | ||||||||||
Voltage range | +20%~-40% Linear rating drop Between -20%~-40% and 100%~50% | ||||||||||
Frequency range | 40~70Hz | ||||||||||
Bypass input | Input voltage | 380/400/415V ( linear voltage ) | |||||||||
Input voltage range | +20%~-50% | ||||||||||
Input Phase | Three phase four wire | ||||||||||
Frequency range | 40~70Hz | ||||||||||
Output | Stable voltage precision ( balanceable load ) | ±0.5% | |||||||||
Dynamic voltage in instantaneous change | ±2% ( 0~100% load change ) | ||||||||||
Voltage aberration ( linear load ) | THD<0.5% ( Phase voltage ) | ||||||||||
Voltage aberration ( Non-linear load ) | THD<5% ( Phase voltage ) | ||||||||||
P.F. | 0.8 ( lag ) | ||||||||||
Frequency track range | 50Hz±3Hz | ||||||||||
Frequency precision ( battery inverter ) | ±0.1% | ||||||||||
3 phase difference | 120±0.5° ( balanceable or un-balanceable load ) | ||||||||||
100% imbalance degree of un-balanceable load voltage | ±3% | ||||||||||
Frequency track speed | <1Hz/s | ||||||||||
Inverter overload capability | 105% 111% 125% | ||||||||||
Bypass overload capability | Run long time when 150% load Hold on 100ms when load>1000% | ||||||||||
System | System efficiency ( linear load ) | 91% | |||||||||
Battery inverter efficiency ( linear load ) | 91% | ||||||||||
Display | LCD+LED | ||||||||||
EMC/EMI | Conduction/ radiation | FCC Part 15, Class A | |||||||||
Harmonic current | IEC6 1000-3-12 | ||||||||||
Anti-jamming | EN 6 1000-4-2 .3.4..6.8.9.11 Level III , EN 6 1000-4-5 Level | ||||||||||
Safety requirement | |||||||||||
Noise ( 1m ) | 55dB | 55dB | 62dB | 62dB | 62dB | 64dB | 65dB | 65dB | |||
Insulated resistance | > 2M (500VDC) | ||||||||||
Insulated intensity | (input, output against ground) 2820Vdc; electricity leakage is less than 3.5mA; no flashover 1min | ||||||||||
Electricity surge protection | Meet IEC60664-1 installation requirement, bear 1.2/50us+8/20us mixed wave capability is not less than 6KV/3KA | ||||||||||
Defence level | IP20 | ||||||||||
Battery quantity | 40PCs /38~42 PCs (optional) x12V battery | ||||||||||
Installation | Wire connection | Up and down wire connection | |||||||||
Physics Environment | Altitude | <3000M | |||||||||
Humidity | 0-95% (non-condensing) | ||||||||||
Working Temperature | 0-40 ℃ | ||||||||||
Storage Temperature | -20-70 ℃ | ||||||||||
Dimension(mm) (LxWxH) | 700x800x1820 | 1000x800x1880 | |||||||||
N.W.(KGs) | 300 | 320 | 340 | 360 | 400 | 550 | 570 | 600 | |||
Measure(mm) (LxWxH) | 790x880x1980 | 1090x880x1980 |