user login

industrial gas alarm

Min. Order: 1 Piece/Pieces
Payment Terms: T/T Western Union
Supply Ability: 20000pcs/month
Place of Origin: Guangdong

Company Profile

Location: China (Mainland)
Business Type: Manufacturer

Product Detail

Model No.: YK-6000F
Usage: Auto
Brand Name: Yongkang
alarm: indutrial gas alarm
Production Capacity: 20000pcs/month
Delivery Date: 15 days
Show

Product Description

Detail:
Indoor gas detector gas sensor by the gas sensing device outside the gas by inhalation when tested Outside gas leak, by the transmitter within the sample for processing the sensor output and ambient gas concentration corresponding to 4 ~ 20mA current signal or Modbus digital signal.
Sensors measure: combustible gas (100% LEL); toxic gas (ppm)
Combustible Gas Detector (% LEL) - used to measure the concentration was lower than the low calibration gas when the target explosive limit (LEL) of combustible gas.
Gas detector is used to detect the atmosphere gases (PPM). Detect carbon monoxide and hydrogen sulfide, etc.
Features
* Use calibration, alarm set points, on-site without opening the lid, long life
* 4 ~ 20mA output signal and RS485 interfaces standard digital signal can be connected with the DCS system
* Relay output linkage
* Live misconnection protection, wiring error in the case of the transmitter is not compromised
* Output signal protection, regardless of any fault, can guarantee that no more than 25mA current signal
* Professionally designed mounting bracket, easy installation.
Specifications 
* Measuring principle: electrochemical catalytic combustion type *Infrared semiconductor-type formula (see the gas list)
* Display: none
* Measuring range: 0-9999ppm; 0-100% LEL; 0-100% Vol
* Accuracy: ≤ ± 3% FS
* Response time: ≤ 15 S
* Set by: the security of infrared remote control
* Output signal: 4-20mA (3 wire) RS485 (4 wire) (maximum load 500 ohms)
* Alarm mode: passive contact output, contact capacity 1A 24VDC
* Transmission distance: 1,500 meters (2.5 mm2 copper cable)
* Operating Voltage: 24V
* Environmental Temperature -40 ℃ - +70 ℃
* Environmental humidity 15 ~ 95% RH
* Dimensions 190 * 180 * 100 (mm)

 
Post Buying Request