user login

RLT10KL online UPS

2555.0~5522.0 USD
Min. Order: 1 Set/Sets
Payment Terms: L/C, T/T
Supply Ability: 50
Place of Origin: Guangdong

Company Profile

Location: China (Mainland)

Product Detail

Model No.: RLT-10KL
Means of Transport: Express / Ocean
Application: Medical
Phase: Three Phase
Type: On-line
Protection: Short Circuit
Brand Name: Resden
Weight: 75KG
Output Voltage: 380V/480V
Protections: Protection against all types of power problem
Efficiency: >91%
MTBF: 300000hr
Warranty: 36 months
Certifications: CE/LTC/UKAS
Production Capacity: 50
Packing: carton
Delivery Date: 15 days
Show

Product Description

DSP Technology: The advanced DSP digital control technology enable UPS more stable performance.
Environment Friendly: ThisUPS is eco-designed and manufactured to meet the China local pollutioncontrol requirement of Electronic Products, which means it will cause noharm to environment and human beings in normal usage.
Zero power switch delay: Whenthe utility power fails, UPS will automatically switch from AC mode tobattery mode with no delay, which will ensures stable power supply ofoperating system.
Sufficient Expansion Slots: Thepre-allocated smart slots enable flexibility in choice of USBcards,AS400 cards, CMC monitoring cards, SNMP cards, RS485 cards and EMDenvironment monitoring cards.
Support the Generators: Thewide range of input voltage and frequency can effectively separate theharmful electric wave produces by the generators and provide safe andreliable power supply.

RLT Technical parameters:
Model

Rate capacity
10kVA
Theory
really online, static bypass switch, dual-transform, output isolation
Input phase
Phase
three-phase+N+G
Voltage
380V±20%
Frequency
50Hz±10%
Max current(A)
19
Power factor
0.95
Soft start
0-100% 5s
Bypass input phase
Phase
three-phase+N+G
Voltage
380V±15%
Frequency
50Hz±5%
Transform time inv-bypass
≤2ms
Battery
DC voltage
384V
Float charge
432V
Halt voltage
336V
Max current of discharge
25
Charge current
10-25A adjustable
Rate capacity
10kVA
Output
Phase
three-phase+N+G
Voltage
380V±1%
Frequency
50Hz±5%(line) 50Hz±0.05%(battery)
Power factor
0.8
Output wave
sine wave
Total harmonic distortion
linear load,<3% non--load<5%
Load dynamic transient emission
±5%(0 100%)
Resume time
<10 ms(±5%)
Unbalanced voltage
<±3% <±1%
Overload capacity
125% 10min 150% 1min >150% 200ms
System
Efficiency
>91%,95%, ECO mode
Communicate port
RS 232/RS 485
Temperature
0-40°C
Relative humidity
0~90%
Noise
50 dB
Outlook
Size D×W×H(mm)
800×560×1400
Weight(Kg)
200
Post Buying Request